Diagnostics
Document No. D109-010
Page 84 of 108
Revision 1.15
DNP3 Message Queue Full
The DNP3 Router has received too many simultaneous messages to
process.
Node Mismatch
The received message node number did not match the DNP3 Router
configured node address.
Select Size Too Large
When the Select/Operate functionality is used the DNP3 Router
supports a maximum of 255 bytes per transaction (or one full DNP3
message).
Select Operate Data Mismatch
The Select/Operate functionality requires that the response to the
Select function matches the Select request.
Table 7.4 – Module error statistics
The following Logix statistics are only relevant when the module is running in either Reactive
Tag or Scheduled Tag mode.
Figure 7.6. - Status monitoring – Logix Statistics
Statistic
Description
Current Connections
The number of current open class 3 connections.
Connection Failures
The number of failed attempts at establishing a class 3 connections with a
Logix controller.
Tag Not Exist Errors
The number of tag read and tag write transactions that failed due to the
destination tag not existing.
Privilege Violation Errors
The number of tag read and tag write transactions that failed due to a
privilege violation error.