Description
This parameter is used to provide a more detail description of the application for the
module.
Major Revision
The major revision of the module
Mapping Mode
The mapping mode will determine how the DNP3 messages are routed.
In Reactive Tag mode the module will automatically route the DNP3 message and
function to the correct Logix tag. In this mode, the DNP3 Router will map the DNP3
request to the preconfigured tag.
DNP3 communication in this mode is initiated by the remote DNP3 device.
In Scheduled Tag mode, the DNP3 Router will initiate the exchange between the
remote DNP3 device and Logix. Either by reading data from a DNP3 device and writing
it into a preconfigured Logix tag or vice versa.
DNP3 communication in this mode is initiated by the DNP3 Router.
In Unscheduled mode the DNP3 Router routes Logix messages to the remote DNP3
device and returns the result. There is little configuration required in the DNP3 Router
as the routing information is configured by Logix for each message transaction.
DNP3 communication in this mode is initiated by Logix.
Refer to the message routing section of the document for a details explanation of the
routing operation.
ENIP Retry Limit
The amount of EtherNet/IP retries the module will make once no response was
received from the Logix Controller.
ENIP Timeout
The time in milliseconds after which a retry is sent. Once the first retry is sent the next
retry will be sent after the same amount of time. This will repeat until the ENIP Retry
Limit is reached.
Controller Type
The DNP3 Router can communicate to either a Rockwell Automation Logix based
controller or a Rockwell Automation Micro820/850 controller. The user can select
either
Logix
or
Micro800
for the controller type.
Refer to the Micro800 Application Note for further information regarding the setup
and operation of the DNP3 Router with the Micro820/850 controllers.
Table 3.1 - General configuration parameters
The general configuration is shown in the figure below. The DNP3 general configuration
window is opened by either double clicking on the module in the tree or right-clicking the
module and selecting