Setup
Document No. D109-010
Page 52 of 108
Revision 1.15
Figure 3.53. - RSLogix General module properties in RSLogix 5000
NOTE:
The user will need to enter the exact connection parameters before the
module will establish a class 1 connection with the Logix controller.
Next the user needs to add the connection requested packet interval (RPI). This is the rate at
which the input and output assemblies are exchanged. The recommended value is 500ms.
Refer to the technical specification section in this document for further details on the limits
of the RPI.
NOTE
: Although the module is capable of running with an RPI of 10ms, it is
recommended to set the RPI to 500ms, to avoid unnecessary loading of the
module processor.
Figure 3.54. - Connection module properties in RSLogix 5000