Revision 1.15
Buffer Size
The size of the Events Array defined in the Logix controller.
NOTE
: This value must not exceed the Logix controller tag array
size. If this is the case the unloading of events to the Logix
controller will not operate correctly.
Unload Count
This parameter is the maximum number of evens that will be uploaded per poll.
This value is between 1 and 10.
Poll Rate
The rate (in seconds) at which the DNP3 Router polls for events from either
classes (e.g. Class 1) or groups (e.g. Group 32 Analog Inputs).
Event Classes
When the Event Unload Mode is
Class Mode
then the user can select how each
event Class must operate. The following options are available:
None
This group will not be queried or allowed to unload events with unsolicited
responses.
Poll
The event class will be polled for events at the poll rate.
Unsolicited
The DNP3 Router will enable Unsolicited Responses for that specific class for each
DNP3 Outstation. This will allow the DNP3 Outstation to send new events as they
are generated rather than being polled (reducing network traffic).
Event Groups
The groups are polled for events at the poll rate selected.
Table 3.4 – Master Events configuration parameters
The Master Events configuration is shown in the figure below. The DNP3 Master Events
configuration window is opened by either double clicking on the module in the tree or right-
clicking the module and selecting
Configuration
.
Figure 3.18 – Master Events configuration