The second part of the Scheduled Tag mode setup is to configure the scan intervals. The scan
intervals allow different data items to be transferred at different rates. There are 4 scan
classes, viz. A, B, C and D. The intervals for each can be adjusted by entering the scan time in
milliseconds. The interval must be between 200 milliseconds and 60 seconds.
The third part of the Scheduled Tag mode setup is to configure the link between a DNP3
group, variation, and range combination to a Logix tag, and the associated action and scan
required.
Figure 3.33. – Scheduled Tag Mapping
The Function field specifies whether the transaction will result in a read or write to the Logix
controller tag.
NOTE: The DNP3 Router supports four different DNP3 functions in scheduled
mode (Read, Select/Operate, Direct-Operate, and Direct-Operate-No-
Response). The Read, Select/Operate, Direct-Operate, and Direct-Operate-No-
Response functions will all translate into a Logix tag write.
The Scan field specifies at what rate the transaction will be executed. Select a scan class letter
that matches the required interval. Care must be taken to select a realistic scan interval,
taking into account the configured Baud rate and message size.
The IP address and Node is the remote device’s IP address and node number.