Logix Operation
Document No. D109-010
Page 58 of 108
Revision 1.15
Tag reading and writing requires the module to first establish
a class 3 connection with the Logix Controller.
TagErrors
DINT
The number of failed tag access (read/write) requests when
operating in tag Map mode.
These may include privileged violations, non-existing tags,
etc.
MasterEventBufferIndex
DINT
The Master Event Tag UDT array index number where the
next event received from the master will be unloaded.
Table 4.1 - RSLogix 5000 input assembly parameters
4.2.2.
O
UTPUT
A
SSEMBLY
The following parameters are used in the output assembly of the module.
Parameter
Datatype Description
RoutingInhibit
BOOL
This bit inhibits the module routing capabilities.
When set, no DNP3 messages will be routed. This may be required
in applications running a redundant DNP3 network where one of
the DNP3 Routers is to run in a hot-standby mode.
Table 4.2 - RSLogix 5000 output assembly parameters
4.3.
UNSCHEDULED MESSAGING
When the DNP3 Router is configured in Unscheduled Mode, it will process DNP3 message
requests sent from Logix via a message instruction.
NOTE: The user will need to build the DNP3 objects for the application layer in
the request data of the unscheduled message.
See Appendix A for more information on this.
To simplify the configuration of the required message a number of UDTs have been
preconfigured, and are available on the Aparian DNP3Router webpage (see the further
information section).
The message instruction should be setup as follows:
Содержание A-DNP3R
Страница 1: ...DNP3 Router User Manual A DNP3R Document No D109 010 09 2017 Revision 1 15...
Страница 64: ...Logix Operation Document No D109 010 Page 64 of 108 Revision 1 15 Figure 4 8 DNP3 Message Response Example...
Страница 93: ...Diagnostics Document No D109 010 Page 93 of 108 Revision 1 15 Figure 7 17 Web interface...