Setup
Document No. D109-010
Page 51 of 108
Revision 1.15
3.8.2.
RSL
OGIX
5000
C
ONFIGURATION
(P
RE
-V
ERSION
20)
3.8.2.1.
ADD MODULE TO I/O CONFIGURATION
The module can operate in both a Logix “owned” and standalone mode. When the module
operates in a Logix “owned” mode the DNP3 Router will need to be added to the RSLogix 5000
IO tree. The module will need to be added as a generic Ethernet module. This is done by right
clicking on the Ethernet Bridge in the RSLogix 5000 and selecting
New Module
after which the
ETHERNET-MODULE
is selected to be added as shown in the figure below.
NOTE: See the next section for importing the configuration (L5X).
Figure 3.52. - Add a Generic Ethernet Module in RSLogix 5000
The user must enter the IP address of the DNP3 Router that will be used. The assembly
instance and size must also be added for the input, output, and configuration in the
connection parameters section. Below are the required connection parameters.
Connection Parameter
Assembly Instance
Size
Input
108
37 (32-bit)
Output
101
1 (32-bit)
Configuration
102
0 (8-bit)
Table 3.8 - RSLogix class 1 connection parameters for the DNP3 Router