Setup
Document No. D109-010
Page 35 of 108
Revision 1.15
When using operate commands the user will always need a tag for the operate command as
well as a tag for the status. For example, when using Binary Commands (switching a binary
value on or off) the Binary Control Group 12 will need to be used. This group is an operate-only
group and does not contain or hold any value. The value received via the Command Group
must then be copied to the Status Group 10 in the Logix controller (as shown in the diagram
below). This is a read only group and is used by the DNP3 Master to monitor the status and
actual value of the outputs. The same must be done for Analog Output Commands and Status
Groups. See the example
DNP3OutstationExample
project.
Figure 3.28 – DNP3 Commands configuration and operation
3.5.2.
S
CHEDULED
T
AG
(M
ASTER
)
M
ODE
The Scheduled Tag routing mode transfers data between DNP3 devices and Logix controllers.
Unlike the Reactive tag mode, the DNP3 Router when in the Scheduled Tag mode initiates the
messaging.
In this mode the DNP3 Router transfers data between a Logix controller and DNP3 devices
without any configuration or programming required in either the DNP3 device or the Logix
controller. The data will be exchanged at a fixed interval which is configured in Slate.