DNP3 Operation
Document No. D109-010
Page 74 of 108
Revision 1.15
The structure of the UDT is provided below.
Figure 5.16 – Master Event Logix UDT
Below is an explanation of each element in the structure:
Attribute
Description
EvtPending
This bit is set when the event is written into the controller. The application code can
use this bit, and subsequently clear it, when the event has been processed.
EvtGroup
This is the DNP3 group which reported the event (e.g. Group 32 – Analog Input Event)
EvtFlags
Each event group has a set of status flags which indicates the states, quality, etc. of the
variable in the event. See the appendix for an explanation of each Group’s set of flags.
EvtSrcNodeAddress The Node Address of the Outstation which reported the event
EvtSrcIPAddress
The IP Address of the Outstation which reported the event (note this is only valid when
the DNP3 Router is setup for either TCP or UDP).
EvtElementIndex
This is the element offset which generated the event (Analog Input 5).
EvtTimeStamp
This is the time (in the Outstation) when the event occurred. Note that the appropriate
variation must be selected in the DNP3 Outstation to allow for reporting of event time.
EvtFloatValue
When the event value is a 32-bit float the value will appear in this attribute.
EvtIntegerValue
When the event value is a 8-bit, 16-bit, or 32bit integer the value will appear in this
attribute.
Table 5.2 – Master Event Logix UDT
Содержание A-DNP3R
Страница 1: ...DNP3 Router User Manual A DNP3R Document No D109 010 09 2017 Revision 1 15...
Страница 64: ...Logix Operation Document No D109 010 Page 64 of 108 Revision 1 15 Figure 4 8 DNP3 Message Response Example...
Страница 93: ...Diagnostics Document No D109 010 Page 93 of 108 Revision 1 15 Figure 7 17 Web interface...