2 6

 Flashing light – pulsing mode.

To consecutively change  a light-sound alarm’s mode it is required to press

[1]

 button. Pressing the

Cancel button causes the going into the programming mode with resetting of the changes made. Pressing the
Select button causes the going into the programming mode with the new mode storage.

8.8 Section  5. Configuration of user’s settings.

8.8.1 Change of user permissions (user rights)

The user access to control the certain loops is regulated by user permissions.
To view and change user permissions it is required to enter:

[5][ N][1]

,  where

[N]

– user’s number (

1 .. 8

).

After that one of red indicators

[1] .. [8]

highlights the user’s number and

[1] .. [8]

yellow indicators

lights indicate those AL the user has rights on.

The user has rights to control a zone if the yellow indicator corresponding to the zone is on, and does

not have rights if the corresponding indicator is off.

Removal/setting rights to control the AL is made by pressing the button with the corresponding zone

number

[1] .. [8]

.

Pressing the Cancel button leads to going into the programming mode with resetting the changes

made. Pressing the Select button leads to going into the programming mode with saving the changes made.

8.8.2 Change of authorized user access code

To change the authorized user access code it is required to enter using the number buttons:

[5][N][2]

,

where

[N]

– user’s number (

1 .. 8

).

After that one of red indicators

[1]..[8]

denoting the user’s number starts flashing with frequency 1

Hz.

Further, enter the new user’s code from 1 to 8 characters long using number buttons then press the

Select button. If the entered code is accepted then 2 intermittent sound signals shall sound for a minute.
During this time it is required to repeat the access code entering and press the Select button.

The successful change of the code is accompanied with 3 short sound signals. If entered codes do not

coincide the panel shall issue one long sound signal of low tonality.

To deter  unauthorized control of the AL it is

recommended

 to change access codes set by default.

Example:

  to set the access code of the 2

nd

 user that is equal

[1][3][1][2]

 you should enter:

[5][2][2]

– 2 short sound signals;

[1][3][1][2] [Select] –

 intermittent sound signals;

[1][3][1][2] [Select] –

 3 short sound signals. The access code of the 2

nd

 user is changed.

8.8.3 Change of engineer access code

Change of the engineer access code   occurs in the same way as the change of the user’s access code

but to enter the procedure of password change it is required to enter

[8][2] [Select]

instead of

 [5][ N][2].

Unlike authorized user code, maximum length of the engineer access code is extended to 10 characters.

8.9 Resetting panel configuration to factory defaults

This operation resets a panel configuration to the settings indicated in Section 8.11. For that it is

required to consecutively press buttons

[8][1] [Select]

  in the programming mode.

After that during 9-10 sec. all four red indicators “Zone” will flash. To confirm the decision made

about resetting to factory defaults you should press the Select button. As a result the panel changes its
configuration in accordance with default settings.

If during the delay none of the buttons has been pressed or any button except for the Select one has

been pressed then the panel returns to the programming mode not downloading default parameters.

8.10 Resetting engineer access code to factory defaults

If the engineer’s access code has been lost which is different to the default access code, then it is

impossible to enter the programming mode in order to change the panel configuration. To change engineer’s
access code to the default code

[1][2][3][4][4][3][2][1]

, follow the steps below:

Содержание ARTON-08F

Страница 1: ...OPERATIONAL MANUAL ARTON 08F FIRE ALARM CONTROL PANEL...

Страница 2: ...6 4 Disablement of light sound alarms 15 7 6 5 Disablement of Fire output signal 15 7 6 6 Disablement of Fault output signal 16 7 6 7 Testing light indicators and internal sounder 16 8 PROGRAMMING GUI...

Страница 3: ...PPENDIX 2 Dimensions 312 APPENDIX 3 Layout of units blocks and components inside the cabinet 32 APPENDIX 4 Main control PCB layout 33 APPENDIX 5 Description of light and sound indication of modes 36 A...

Страница 4: ...e from 5 to 40 relative air humidity up to 95 at 40 atmospheric air pressure 86 107 kPa 2 3 The panel is intended for identifying and displaying the following statuses of alarm loops Standby mode Atte...

Страница 5: ...wing parameters and functions AL operation logics with verification without verification 2 detectors triggering AL type active passive combined combined passive detector s trigger priority combined ac...

Страница 6: ...he panel as O C from 0 to 3 m 3 15 AL current interpreted by the panel as S C 24 m 3 16 The panel has protection against S C in AL circuits and outputs with indication of a fault 3 17 The panel respon...

Страница 7: ...ly damaged and check the kit for completeness that should comply with Table 4 1 Table 4 1 Name Quantity Note ARTON 08F fire alarm control panel 1 Operational manual 1 Spare parts and accessories 1 Acc...

Страница 8: ...t Open circuit Disabled Attention Verification Optical indicators are located on the front of the enclosure that indicate modes of the panel and each loop status see Appendix 5 5 2 2 Access levels Fou...

Страница 9: ...conditions of Out1 Out2 in the mode of auxiliary adjustable light or sound alarm response to FIRE status in AL response to FAULT status in AL response to general FAULT status response to Detector tri...

Страница 10: ...he fixed value see Table 8 1 relatively to standby basic current Passive The panel responses only to current decrease in the AL at the same time the panel concludes about detectors activation in the A...

Страница 11: ...ed to AL mask Fault in AL included to AL mask General FACP Fault A detector trigger in the AL included to AL mask Transition to FACP Alarm status Example You can program one of outputs e g K11 with th...

Страница 12: ...neral indicator Disabled and also correspondingly disabled Zone1 Zone8 Sounder Fire output Fault output indicators Note The detailed description of light and sound indication of Disabled mode is shown...

Страница 13: ...the panel Note A resistor with from 1 to 10 kOhm resistance should be connected parallel to each pair of alarm s terminals in immediate proximity to the alarm to control circuit integrity of alarms T...

Страница 14: ...s The button should be kept pressed until the sound signal is silenced When the sound has been muted the AL becomes disabled and the yellow light indicator of the AL and the Disabled general indicator...

Страница 15: ...should be pressed in the authorized user mode while keeping pressed the Select button Making the same actions again allows to report the Fault signal to CMS in the Fault mode Disablement of the Fault...

Страница 16: ...jects Out1 and Out2 high current outputs See Table 8 2 Section 3 configuration of K1 K4 outputs There are 4 objects K1 K4 low current ouputs See Table 8 3 Section 4 configuration of light and sound al...

Страница 17: ...on leads to resetting the whole entered sequence Correspondently after pressing the Cancel button the section code parameter code parameter value should be entered Note The following parameters are th...

Страница 18: ...d active detector trigger priority 1 n 3 24 disabled AL reset time 11 5 sec by default 12 10 sec 13 15 sec 14 20 sec 21 25 sec 22 30 sec 23 35 sec 1 n 4 24 40 sec AL verification time 11 10 sec 12 20...

Страница 19: ...nder 11 disabled passive state continuous enabled active state by default 12 enabled passive state disabled active state 13 disabled passive state pulse mode active state 14 enabled passive state puls...

Страница 20: ...press the appropriate buttons Consecutive pressings result in turn by turn change of yellow indicator luminescence enabled disabled Pressing to the Select button results to going to programming mode...

Страница 21: ...tivates provided that AL1 or both loops AL3 and AL4 will go to the Fire condition To change combination of loops involved into the activation condition of loops press the corresponding zone button Thu...

Страница 22: ...Mask of loops involved to activation condition of the output see Note 8 6 1 Type of load control of Kn output 11 Control only S C by default 12 Control only O C 1 10 kOhm resistor is required to be i...

Страница 23: ...tput activates provided that AL1 or both loops AL3 and AL4 will go to the Fire condition To change combination of loops involved into the activation condition of loops press the corresponding zone but...

Страница 24: ...30 sec 21 1 min 22 3 min by default 23 10 min 24 30 min 31 1 h 32 3 h 33 10 h 4 N 3 34 Not limited till resetting the activation condition Type of load control of the output 11 Control only S C 12 Con...

Страница 25: ...he access code entering and press the Select button The successful change of the code is accompanied with 3 short sound signals If entered codes do not coincide the panel shall issue one long sound si...

Страница 26: ...of Out1 and Out2 outputs 4 wire AL power output Load control of Out1 and Out2 outputs only S C control Time of transition processes at outputs switching 150 msec K1 K4 mode is disabled passive state C...

Страница 27: ...and stamp fault type place of the panel s installation customer s address 11 SPARE PARTS AND ACCESSORIES LIST Table 12 1 Name Quantity 1 Fuse 0 5 1 2 Fuse 1 0 1 3 Resistor 3 3 kOhm 0 25W 11 4 Resisto...

Страница 28: ...L S Fire output fault of the Fire output Fir Fault output fault of the Fault output Flt System system error 4 red indicator Fire is used for indication of FIRE mode 5 red indicator Alarm is used for i...

Страница 29: ...n the lower line are dual colour Yellow light indicates AL status FAULT and DISABLEMENT Green light indicates parameter s value in the programming mode 13 Buttons 1 8 of the Zone group are for enterin...

Страница 30: ...31 APPENDIX 2 Dimensions...

Страница 31: ...ng of the transformer and grounding 8 terminal block with fuse holder 0 5 for connection of the panel to 220 V A C mains 9 mains transformer 10 grounding terminal 11 holes for introducing wires and ca...

Страница 32: ...common minus wire Ch1 Ch8 connection of AL Out1 Out2 programmable outputs max load current should not exceed 300 mA They can be programmed as 4 wire power outputs outputs of ight sound alarms or as no...

Страница 33: ...0 mA Depending on the CP s settings they can be used as outputs of external indication of the status Standby mode Fire or as outputs for transmission of the FIRE notification on logical condition acti...

Страница 34: ...ns failure SB is charged Yellow 0 5Hz Porosity 8 Green Yellow 0 5Hz Porosity 8 Fault 9 220 V mains failure U SB 10 9 V SB is discharged Yellow 0 5Hz Porosity 8 Green 1Hz Yellow 0 5Hz Porosity 8 Fault...

Страница 35: ...scripts in cells of the table 1Hz 2Hz 0 5Hz if they are present denote the frequency of the indicator s flashing and the absence of scripts of frequency denotes steady light of the indicator script Po...

Страница 36: ...54 2 2003 up to 32 detectors can be interconnected in one AL CLR 680Ohm 1 2kOhm EOL resistor 3kOhm 3 6kOhm Typical heat detector circuit wiring models TPT 2 TPT 3 SPT 1A SPT 2A SPT 3A Figure 6 2 The n...

Страница 37: ...more than 15 Up to 25 passive detectors can be interconnected in one AL CLR_a active detectors 680 Ohm CLR_p passive detectors 1 2 kOhm EOL resistor 2 4 kOhm Example of wiring of detectors like SPD 3...

Страница 38: ...gure 6 5 The number of detectors in AL should be such that the total current consumption of all detectors in standby mode would be not more than 3 mA According to EN 54 2 2003 up to 32 detectors can b...