8.6 Section 3. Configuration of « 1» .. « 4» outputs
Table 8.3
Section
Output
number
n
Code and name
of parameter
Parameter’s
value
Description
Setting of Kn output mode
11
disabled – passive state, enabled – active state
(
by default
)
12
Enabled – passive state, disabled – active state
13
Disabled – passive state, pulsing mode – active state
14
Enabled – passive state, pulsing mode in active state
3
n
2
15
Enabled – passive state, pulsing mode in active state
if one of AL involved to activation condition is
disabled by an authorized user.
Setting of Kn output activation time
11
1 sec.
12
5 sec.
13
10 sec.
14
30 sec.
21
1 min.
22
3 min.
23
10 min.
24
30 min.
31
1 h
32
3 h
33
10 h
3
n
3
34
Not limited (till resetting of activation condition)
(
by default
)
3
n
4
Output’s activation condition
(see Note 8.5.1 in the previous section)
3
n
5
Mask of loops involved to activation condition of the output,
(see Note 8.6.1)
Type of load control of Kn output
11
Control only “S/C” (
by default
).
12
Control only “O/C” (1-10 kOhm resistor is required
to be installed parallel to load)
13
Control «S/C» and «O/C».
3
n
6
14
No control.
Time of transition processes at Kn switching
11
150 msec (
by default
)
12
200 msec
13
250 msec
3
n
7
14
300 msec
Frequency of output’s pulsing mode
11
0,5 Hz
3
n
8
12
1 Hz (
by default
)
Note 8.6.1
AL mask determines the AL involved to
«Kn»
activation condition.
From 1 to 8 alarm loops with AND/OR operation logics can be involved to activation condition of
each output. When programming the parameter one of red LED displays the output’s number, and
[1]..[8]
yellow indicators light indicates the loops involved to activation condition of the output. Thus the
steady
light of yellow zone indicator means the zone going to activation condition by
AND
, and flashing of zone
yellow indicator means entering the activation condition of the output by
OR
.
Содержание ARTON-08F
Страница 1: ...OPERATIONAL MANUAL ARTON 08F FIRE ALARM CONTROL PANEL...
Страница 30: ...31 APPENDIX 2 Dimensions...