3 4
Light -
to connect light alarm (LIGHT);
Sound -
to connect sound alarm (SOUND);
Norm
– Norm output;
Fire
– Fire output to CMS;
Fault
– Fault output to CMS;
Alarm
– Alarm output to CMS;
Norm
– Norm output to CMS;
K1..K4
– low current programmable outputs (max load current should not exceed 50
mA). Depending on the CP’s settings they can be used as outputs of external indication of the status
(Standby mode, Fire) or as outputs for transmission of the FIRE notification on logical condition
(activation condition).
Note. To control the integrity of communication lines of outputs «Light» «Sound»
«Fire» «Fault» it is necessary parallel to loads to connect resistors (from 2 kOhm to 10
kOhm - not indicated on the diagram). Resistors should be connected up from the side of load.