7
3 TECHNICAL SPECIFICATIONS
3.1 The panel is 220 (+22-33) V mains-powered with frequency (50±1) Hz and/or 12 V hermetic non-
serviced lead-acid storage battery powered, 7/7.2 A/h nominal capacity and 10,5 V terminal voltage of long-
lasting discharge (SB is not supplied with the panel).
3.2 Max mains power consumption – 30 W.
3.3 Standby mains power consumption – 15 W.
3.4 Max SB current consumption – 1,0 .
3.5 Standby max SB current consumption – 0,2 .
3.6 Max SB current consumption when mains power is off and SB voltage < (10,5 - 1) V - 50 m .
3.7 Voltage on contacts of open outputs at total output key load < 0,8 A is 8,8-14 V. Double pulsation
amplitude does not exceed 0,5 V.
3.8 Max voltage on deenergized Light, Sound, Fire and Fault outputs at 3,3 kOhm load resistance (with
resistors supplied with the panel) - 2,5 V.
Note.
Presence of the voltage is connected with the need to control the outputs load circuit. With real
loads (e.g., relay winding) the voltage value is close to zero.
3.9 Max number of loops connectable to the panel – 8.
3.10 Supply voltage on AL1-AL8 contacts at load absence – 15 ( 1) V.
AL1-AL8 voltage at 20 mA current in each AL - 12 V.
3.11 Total line (wire) resistance of AL not considering EOL resistor impedance - <220 Ohm.
3.12 Resistance of leakage between AL lines (if EOL resistor is disabled), and also between each AL line
and enclosure - 50 kOhm.
3.13 Min current change in AL circuit (relatively to fixed basic AL current) interpreted by the panel as
FIRE - +4 mA or – 1,2 mA.
3.14 AL current interpreted by the panel as O/C– from 0 to 3 m .
3.15 AL current interpreted by the panel as S/C– > 24 m .
3.16 The panel has protection against S/C in AL circuits and outputs with indication of a fault.
3.17 The panel responses to the AL status change that lasts at least 100 ms and does not issue messages
about the change that lasts less than 50 ms.
3.18 The panel allows to interconnect up to 32 active detectors (SPD-3.1M, SPD-3.5, SPD-3.10, SPT-2B,
SPT-3 etc.). The max standby current consumption by all active fire detectors that are in the AL, should not
exceed 3 mA.
3.19 Automatic AL reset duration (time of switching-off) when AL is being verified or manually reset - >
5 sec. (You can set from 5 to 40 sec).
3.20 Expectation time of repeated activation in Attention mode after AL resetting, when the one has
been detected the panel goes to Fire mode - (60 1) sec. You can set from 10 to 240 sec.
3.21 Max load current on the Light and Sound outputs – 300 mA.
3.22 Max load current on Out1 and Out2 outputs - 300 mA;
3.23 Max load current on Fire, Fault, Alarm, Norm, K1 – K4outputs – 40 mA;
Note. Total load current of all outputs should not exceed 0,8 A at maximum voltage on open
outputs. This requirement is stipulated only by time decrease of stand-alone operation of the
panel powered by SB when exceeding the value.
3.24 Min current load values of the panel in SM for each output: Light, Sound, Fire, Fault and also in
AL1-AL8 circuits – 3,5 mA (set by 3.3 kOhm resistors from spare parts and accessories package, see Section
12)
3.25 Technical readiness time after the panel has been powered – <20sec.
3.26 Average mean-time-between-failures - > 40000 hs.
3.27 Average lifespan - > 10 years.
3.28 Dimensions – 230 280 90 mm.
3.29 Weight without SB – 3,5 kg.