![AP ARTON-08F Скачать руководство пользователя страница 20](http://html1.mh-extra.com/html/ap/arton-08f/arton-08f_operational-manual_2951617020.webp)
2 1
12
Control S/C alone
(fixing 1-10 kOhm resistor parallel to load is
required)
13
Control S/C and O/C
14
No control
Time of transitional processes at output’s switching
11
150 msec (
default
)
12
200 msec
13
250 msec
2
n
7
14
300 msec
Frequency of pulse mode in output’s active state
11
0,5 Hz
2
n
8
12
1 Hz (
by default
)
Note 8.5.1
When output’s activation condition is programmed the zone’s red indicator indicates the number of
output and
[1]..[5]
yellow LED light means events involved in the output’s activation condition. At that
steady yellow indicator light means entering activation condition.
Output’s activation condition (if
Outn is output to sounder):
- 1
st
LED (lit/not lit) – response to FIRE state in AL (enabled/disabled)
- 2
nd
LED (lit/not lit) – response to FAULT state in AL (enabled/disabled)
- 3
rd
LED (lit/not lit) – response to FAULT general state in AL (enabled/disabled)
- 4
th
LED (lit/not lit) – response to Detector’s trigger state in AL (enabled/disabled)
- 5
th
LED (lit/not lit) y– response to ALARM general state in AL (enabled/disabled)
Exa mpl e:
if a ft er e nt er ing
[2][1][4]
(act ivat io n co nd it io n o f «
Out1
»)
[1]
and
[4]
in d ica to rs are o f f, t he n «
Out1
» act ivat es onl y a ft er ar ising o f
“FI RE in AL” o r “D et ecto r’s tr ig ger in A L” e ve nt s.
To change combinations involved in event activation condition press the appropriate buttons. Consecutive
pressings result in turn-by-turn change of yellow indicator luminescence (enabled/disabled).
Pr ess ing t o t he Se lect but t o n resu lt s t o going t o pro gramming mo de w it h
r ese t o f cha n g es made. P r es sin g the S e le ct but t o n r esult s in go in g t o
pro gra mming mo de wit h saving o f t he new act ivat io n co nd it io n fo r t he output.
Note 8.5.2
If Outn is set as power output of 4-wire AL
then the parameter sets mask of 4-wire AL powered
from the output.
When the AL mask is being set, the red lit LED indicates the number if output, and steady light of
yellow indicators
[1] ... [8]
means numbers of 4-wire AL powered from the output.
To change AL mask press the appropriate AL buttons, at that consecutive pressings result in turn-by-
turn change of yellow AL LED luminescence – on/flash/off.
Pressing the Cancel button results in going to programming mode saving new AL mask in energy-
independent memory.
If «Outn» is set as output to light or sound alarm,
then the parameter sets loops involved in
activation condition of «Out
n
».
In activation condition of each output from 1 to 8 AL with operation logics by AND/OR can be
involved. When programming one of red LED displays the output number and light of
[1]..[8]
yellow
indicators denotes the AL involved into activation condition of the output. The
steady
light of yellow
indicator means entering to activation condition of the AL by
AND
, and flashing of zone yellow indicator
denotes entering of the AL by
OR
.