1 8

The object number is indicated by one of red indicators

[1]..[8],

  and  the  parameter  value  (two  figures)  is

indicated by the consecutive flashes of the corresponding green indicators

[1]..[8]

with short span between

flashes. In 3-4 sec. the indication cycle is repeated again. The value of the selected parameter is defined by
the sequence of green LED flashes. So, e.g., two flashes of green LED

[1]

 correspond to the parameter value

«

11

».  The  green  LED  flash

[2]

, and after that the green LED

[1]

 flash correspond to the parameter value

«

21

» and so on.

If you enter the new value while the current parameter value is indicated then the new entered

parameter value will be induced.

Correct entry of a new parameter value is confirmed by the 2-tone short sound signal. Entry of non-

existing or impermissible parameter value is indicated by one long sound signal of low tonality, after that
entering of parameter value can be made one more time.

To exit the ‘parameter entering code’ mode saving the new value in energy-dependent memory press

the Select button. It will be confirmed by three short sound signals.

To return to the programming mode without saving changes made press the Cancel button or wait a

minute (automatic return) if the button has not been pressed.

Not e:

 Pressing the Cancel button at any moment of sequence entry leads to clearing of input

buffer and resetting to the beginning of entering. So, if at any stage the incorrect code has
been entered pressing the Cancel button leads to resetting the whole entered sequence.
Correspondently, after pressing the Cancel button the section code, parameter code, parameter
value should be entered.

Not e:

The following  parameters are the exceptions to the general rules:

-

Section [1] parameter [2];

-

Section [2] parameters [4] and [5];

-

Section [3] parameters [4] and [5];

-

Section [5] parameter [1].

-

Fo r det ai led d es c ript ion  o f the pa ra met e rs co nfi gu rat ion  p lease  refe r to
the co rresponding sections.

8.3 Fixing AL basic current

Attention! This procedure is strongly required to be made when installing every new or

making change to the existing alarm loop.

Basic AL current is the AL current defined in the panel as the AL standby mode current. The current

is involved in identification of detectors’ triggering in the AL.

Before this procedure is applied, the AL with a terminal element, where the basic current is to be

fixed, should be wired to the panel while all detectors in AL should be in standby condition.

To fix the AL basic current in the ‘parameter code entering’ mode enter the following number

sequence:

[1][2][N]

,

where

[N]

– zone number (1 .. 8).

When  entering is complete the red indicator of the AL being measured shall be lit and the yellow

indicator of the AL shall flash a few times signaling the measurement of AL drawing current.  When the
procedure is over all indicators shall be off and the internal sounder shall issue:

– 3 short sound signals if the setting of basic current in the AL has been successfully made;
– 1 long sound signal of low tonality if the measured AL current is beyond the limits of

permissible current range (e.g. AL in S/C or O/C state).

After that the panel goes into the ‘parameter entering code’ mode.

Содержание ARTON-08F

Страница 1: ...OPERATIONAL MANUAL ARTON 08F FIRE ALARM CONTROL PANEL...

Страница 2: ...6 4 Disablement of light sound alarms 15 7 6 5 Disablement of Fire output signal 15 7 6 6 Disablement of Fault output signal 16 7 6 7 Testing light indicators and internal sounder 16 8 PROGRAMMING GUI...

Страница 3: ...PPENDIX 2 Dimensions 312 APPENDIX 3 Layout of units blocks and components inside the cabinet 32 APPENDIX 4 Main control PCB layout 33 APPENDIX 5 Description of light and sound indication of modes 36 A...

Страница 4: ...e from 5 to 40 relative air humidity up to 95 at 40 atmospheric air pressure 86 107 kPa 2 3 The panel is intended for identifying and displaying the following statuses of alarm loops Standby mode Atte...

Страница 5: ...wing parameters and functions AL operation logics with verification without verification 2 detectors triggering AL type active passive combined combined passive detector s trigger priority combined ac...

Страница 6: ...he panel as O C from 0 to 3 m 3 15 AL current interpreted by the panel as S C 24 m 3 16 The panel has protection against S C in AL circuits and outputs with indication of a fault 3 17 The panel respon...

Страница 7: ...ly damaged and check the kit for completeness that should comply with Table 4 1 Table 4 1 Name Quantity Note ARTON 08F fire alarm control panel 1 Operational manual 1 Spare parts and accessories 1 Acc...

Страница 8: ...t Open circuit Disabled Attention Verification Optical indicators are located on the front of the enclosure that indicate modes of the panel and each loop status see Appendix 5 5 2 2 Access levels Fou...

Страница 9: ...conditions of Out1 Out2 in the mode of auxiliary adjustable light or sound alarm response to FIRE status in AL response to FAULT status in AL response to general FAULT status response to Detector tri...

Страница 10: ...he fixed value see Table 8 1 relatively to standby basic current Passive The panel responses only to current decrease in the AL at the same time the panel concludes about detectors activation in the A...

Страница 11: ...ed to AL mask Fault in AL included to AL mask General FACP Fault A detector trigger in the AL included to AL mask Transition to FACP Alarm status Example You can program one of outputs e g K11 with th...

Страница 12: ...neral indicator Disabled and also correspondingly disabled Zone1 Zone8 Sounder Fire output Fault output indicators Note The detailed description of light and sound indication of Disabled mode is shown...

Страница 13: ...the panel Note A resistor with from 1 to 10 kOhm resistance should be connected parallel to each pair of alarm s terminals in immediate proximity to the alarm to control circuit integrity of alarms T...

Страница 14: ...s The button should be kept pressed until the sound signal is silenced When the sound has been muted the AL becomes disabled and the yellow light indicator of the AL and the Disabled general indicator...

Страница 15: ...should be pressed in the authorized user mode while keeping pressed the Select button Making the same actions again allows to report the Fault signal to CMS in the Fault mode Disablement of the Fault...

Страница 16: ...jects Out1 and Out2 high current outputs See Table 8 2 Section 3 configuration of K1 K4 outputs There are 4 objects K1 K4 low current ouputs See Table 8 3 Section 4 configuration of light and sound al...

Страница 17: ...on leads to resetting the whole entered sequence Correspondently after pressing the Cancel button the section code parameter code parameter value should be entered Note The following parameters are th...

Страница 18: ...d active detector trigger priority 1 n 3 24 disabled AL reset time 11 5 sec by default 12 10 sec 13 15 sec 14 20 sec 21 25 sec 22 30 sec 23 35 sec 1 n 4 24 40 sec AL verification time 11 10 sec 12 20...

Страница 19: ...nder 11 disabled passive state continuous enabled active state by default 12 enabled passive state disabled active state 13 disabled passive state pulse mode active state 14 enabled passive state puls...

Страница 20: ...press the appropriate buttons Consecutive pressings result in turn by turn change of yellow indicator luminescence enabled disabled Pressing to the Select button results to going to programming mode...

Страница 21: ...tivates provided that AL1 or both loops AL3 and AL4 will go to the Fire condition To change combination of loops involved into the activation condition of loops press the corresponding zone button Thu...

Страница 22: ...Mask of loops involved to activation condition of the output see Note 8 6 1 Type of load control of Kn output 11 Control only S C by default 12 Control only O C 1 10 kOhm resistor is required to be i...

Страница 23: ...tput activates provided that AL1 or both loops AL3 and AL4 will go to the Fire condition To change combination of loops involved into the activation condition of loops press the corresponding zone but...

Страница 24: ...30 sec 21 1 min 22 3 min by default 23 10 min 24 30 min 31 1 h 32 3 h 33 10 h 4 N 3 34 Not limited till resetting the activation condition Type of load control of the output 11 Control only S C 12 Con...

Страница 25: ...he access code entering and press the Select button The successful change of the code is accompanied with 3 short sound signals If entered codes do not coincide the panel shall issue one long sound si...

Страница 26: ...of Out1 and Out2 outputs 4 wire AL power output Load control of Out1 and Out2 outputs only S C control Time of transition processes at outputs switching 150 msec K1 K4 mode is disabled passive state C...

Страница 27: ...and stamp fault type place of the panel s installation customer s address 11 SPARE PARTS AND ACCESSORIES LIST Table 12 1 Name Quantity 1 Fuse 0 5 1 2 Fuse 1 0 1 3 Resistor 3 3 kOhm 0 25W 11 4 Resisto...

Страница 28: ...L S Fire output fault of the Fire output Fir Fault output fault of the Fault output Flt System system error 4 red indicator Fire is used for indication of FIRE mode 5 red indicator Alarm is used for i...

Страница 29: ...n the lower line are dual colour Yellow light indicates AL status FAULT and DISABLEMENT Green light indicates parameter s value in the programming mode 13 Buttons 1 8 of the Zone group are for enterin...

Страница 30: ...31 APPENDIX 2 Dimensions...

Страница 31: ...ng of the transformer and grounding 8 terminal block with fuse holder 0 5 for connection of the panel to 220 V A C mains 9 mains transformer 10 grounding terminal 11 holes for introducing wires and ca...

Страница 32: ...common minus wire Ch1 Ch8 connection of AL Out1 Out2 programmable outputs max load current should not exceed 300 mA They can be programmed as 4 wire power outputs outputs of ight sound alarms or as no...

Страница 33: ...0 mA Depending on the CP s settings they can be used as outputs of external indication of the status Standby mode Fire or as outputs for transmission of the FIRE notification on logical condition acti...

Страница 34: ...ns failure SB is charged Yellow 0 5Hz Porosity 8 Green Yellow 0 5Hz Porosity 8 Fault 9 220 V mains failure U SB 10 9 V SB is discharged Yellow 0 5Hz Porosity 8 Green 1Hz Yellow 0 5Hz Porosity 8 Fault...

Страница 35: ...scripts in cells of the table 1Hz 2Hz 0 5Hz if they are present denote the frequency of the indicator s flashing and the absence of scripts of frequency denotes steady light of the indicator script Po...

Страница 36: ...54 2 2003 up to 32 detectors can be interconnected in one AL CLR 680Ohm 1 2kOhm EOL resistor 3kOhm 3 6kOhm Typical heat detector circuit wiring models TPT 2 TPT 3 SPT 1A SPT 2A SPT 3A Figure 6 2 The n...

Страница 37: ...more than 15 Up to 25 passive detectors can be interconnected in one AL CLR_a active detectors 680 Ohm CLR_p passive detectors 1 2 kOhm EOL resistor 2 4 kOhm Example of wiring of detectors like SPD 3...

Страница 38: ...gure 6 5 The number of detectors in AL should be such that the total current consumption of all detectors in standby mode would be not more than 3 mA According to EN 54 2 2003 up to 32 detectors can b...

Отзывы: