2 7
– deenergize the panel from the 220 V A.C. mains and also disconnect the storage battery
from the panel;
– close the contacts of the Reset joint of the main control PCB with a jumper strap (see
Appendix 4) and then connect the panel to 220 V A.C. mains. On energizing the series of 3 short
sound signals with the long interval between series shall sound;
– turn off the power supply of the panel then remove the jumper strap. On the following
turning on the power supply the panel will be activated with the factory engineer access code.
8.11 Factory defaults
AL1 zone type of– fire, without verification.
AL2 zone type – fire, without verification.
AL3 zone type – fire, without verification.
AL4 zone type – fire, without verification.
AL5 zone type – fire, without verification.
AL6 zone type – fire, without verification.
AL7 zone type – fire, without verification.
AL8 zone type – fire, without verification.
Reset time of each AL –
5 sec
.
Verification time of each AL –
60 sec
.
Current growth threshold of active detector in each AL –
4,0 mA
.
Current drop threshold of passive detector in each AL –
1,2 mA
.
Feedback for intellectual detectors in AL –
no feedback
.
Functional purpose of Out1 and Out2 outputs –
4-wire AL power output
;
Load control of Out1 and Out2 outputs -
only S/C control
;
Time of transition processes at outputs switching –
150 msec
;
K1..K4 mode is disabled – passive state,
Continuously enabled – active state.
K1 output is active when there are Fire signals on AL1 and AL2.
K2 output is active when there are Fire signals on AL3 and AL4.
K3 output is active when there are Fire signals on AL5 and AL6.
K4 output is active when there are Fire signals on AL7 and AL8.
Activation time of output – not limited (till removing activation conditions);
Type of output’s load control -
only S/C control
;
Time of transition processes at outputs switching –
150 msec
;
Mode of the LIGHT and SOUND alarms –
off – passive state, pulsing – active state
;
Time of activation –
3 min
;
Type of output’s load control -
S/C and O/C control
;
Time of transition processes at outputs switching –
150 msec
;
Pulsing mode frequency in output’s active state –
1 Hz
;
1st user. Access code –
[1][1][1][1]
. Rights on all AL.
2nd user. Access code –
[1][1][1][2]
. Rights on all AL.
3rd user. Access code –
[1][1][1][3]
. Rights on all AL.
4th user. Access code –
[1][1][1][4]
. Rights on all AL.
5th user. Access code –
[1][1][1][5]
. Rights on all AL.
6th user. Access code –
[1][1][1][6]
. Rights on all AL.
7th user. Access code –
[1][1][1][7]
. Rights on all AL.
8th user. Access code –
[1][1][1][8]
. Rights on all AL.
Engineer access code –
[1][2][3][4][4][3][2][1]
.