Reset of the Fire mode can be made by any authorized user (on entering the access code) by pressing on
the Reset button for 2-3 sec.
5.3.3 Fault mode
The panel identifies the following types of faults: AL S/C and AL O/C, S/C or load break of an output (at
corresponding settings), AL/Output Power Supply Failure, 220 V Mains Failure, Critical discharge or Storage
battery failure, Charger Fault, System error.
The general indicator Fault flashes in Fault mode, the internal buzzer issues the Fault signal, and the
Fault output activates (switches off) transmitting the signal to CMS. Depending on the fault type the
following indicators flash yellow:
«Zone1» .. «Zone8» – AL fault;
«Sounder» – fault of a light-sound alarm;
«Fire output» – Fire output fault;
«Fault output» – Fault output fault;
«System» – system error.
The of the Fault mode is reset automatically (if the fault cause is removed) or by any authorized user
(after entering the access code) by pressing the Reset button for 2-3 sec.
Note. The detailed description of light and sound indication of every fault type is shown in
Appendix 5.
5.3.4 Disabled mode
The Disabled mode is activated as a result of the following actions of an authorized user:
– AL disablement;
– Light and sound alarm disablement («
Light
», “
Sound
”);
– Fire output signal disablement («
Fire
»);
– Fault output signal disablement («
Fault
»
)
;
The mode is indicated by the steady light of the general indicator Disabled and also correspondingly
disabled Zone1…Zone8, Sounder, Fire output, Fault output indicators.
Note. The detailed description of light and sound indication of Disabled mode is shown in
Appendix 5.
5.3.5 Alarm mode
The panel goes into alarm in the following events:
– at the moment of the panel’s lid opening in the standby mode (triggering of tamper contact);
– after 4-time incorrect entering of access code. The Alarm indicator flashes in the mode, the
Alarm output activates (turns off) reporting the signal to CMS and light and sound alarms
(«
Light
», «
Sound
») activate.
Reset of Alarm mode occurs after correct entering of access code by any user.
6 SAFETY ISSUES
6.1 Attention! All operations with the panel must be made by authorized users with closed panel’s lid.
6.2 The installation, mounting, connection and maintenance must be performed by
service personnel
.
6.3 It should be kept in mind that 220 V mains voltage in operating state is connected to input terminals
that is dangerous for human life.
6.4 Installation, removing, wiring and repair of the panel should be made only when the A.C. mains is
off.
6.5 The mounting works with the panel are allowed to be done with an electrical tool with 42 V max and
40 W max that has healthy isolation of current leading circuits from the electrical tool housing.
6.6 The fire safety rules should be kept when performing works with the panel.
6.7 The use of the panel without its enclosure earthing is forbidden.
6.8 The use of the panel in premises with aggressive admixtures causing corrosion is prohibited.