1 7
8 PROGRAMMING GUIDE
8.1 General overview
8.1.1 Entering the Programming mode
To access the programming mode enter the
engineer’s access code
(factory default -
[1][2][3][4][4][3][2][1]
) by consecutive entering
[1]…[8]
buttons from the Zone group and confirm by
pressing the
Select
button. Two short sound signals of different tonality from the internal sounder shall be
heard after that and the Programming indicator shall be lit.
If you enter an incorrect access code 4 times in succession, the panel goes to Alarm mode.
Note. The entered access code before its confirmation can be reset by pressing the Cancel
button. The code should be entered from the very beginning after resetting.
8.1.2 Exiting the Programming mode
To exit the Programming mode enter [8][8][Select] using buttons from the Zone group. The
panel shall reset and it shall go to standby mode provided there are no faults.
8.2 Description of programming
Programming the panel changes its parameter values. All parameters are grouped and divided into
sections with each section having its code. The same type objects (with the parameter collection typical for
the section) are grouped in each section.
Section 1
– configuration of AL. AL1..AL8 are included to the section. See Table 8.1.
Section 2
– configuration of Out1 and Out2 outputs. The section incorporates only 2 objects: Out1
and Out2 high current outputs. See Table 8.2.
Section 3
– configuration of K1..K4 outputs. There are 4 objects – K1..K4 low current ouputs. See
Table 8.3.
Section 4
– configuration of light and sound alarms. Outputs of “Light” and “Sound” alarms. See
Table 8.4.
Section 5 –
configuration of user settings (authorized user and engineer). 8 objects – users.
Section 6
– auxiliary settings.
Each parameter in the section has its own code.
E.g . :
for Sect ion 1 (configurat io n of AL):
Sect io n
1.
O bject nu mber:
1 . . 8
; Code
1
– S et t in g o f A L o pe ra t io n a lg o r it hm;
Sect io n
1.
O bject nu mber:
1 . . 8
; Code
2
– F ix at io n o f b as ic c ur r e nt ;
Sect io n
1.
O bject nu mber:
1 . . 8
; Code
3
– set t ing o f A L t ype ;
Sect io n
1.
O bject nu mber:
1 . . 8
; Code
4
– set t ing o f AL r es et t ime.
Change of parameter values for each object, as a rule, is the consecutive entering of number sequence
on the keyboard consisting of 5 figures:
[section code]
(1 figure)
[object number]
(1 figure)
[parameter code]
(1 figure)
[new parameter value]
(2 figures)
[Select].
Parameter codes and parameter values are shown in each section table.
E.g.
Yo u need to set t he AL2 o perat io n a lgo rit hm wit h ver if icat io n. T o do it yo u
sho u ld e nt er
[1][2][1] [1][2] [Select]
in t he pro gra mming mo de
. W he re:
[1] (section code)
[2] (number of object) [1] (parameter code) [1][2] (new parameter value)
configuration of AL AL number AL operation algorithm with verification
Besides the change of parameter values of objects the programming mode allows to review current
parameter values. The current parameter value is displayed after entering the third figure of parameter code.
Содержание ARTON-08F
Страница 1: ...OPERATIONAL MANUAL ARTON 08F FIRE ALARM CONTROL PANEL...
Страница 30: ...31 APPENDIX 2 Dimensions...