Non-commutable power output of auxiliary devices (+12V, 300 mA max, S/C protected).
For 4-wire power output a mask (kit) of loops powering from the output is set. The other AL
included to the kit shall be automatically reset when resetting the AL.
AL mask can be installed for output adjusted as one to auxiliary light and sound alarm. The loops
can tale parting activation of output with operation logics by AND/OR considering activation
conditions.
To activate an output as sounder you can use the following activation conditions (from one to five):
-
Fire in AL included to AL mask;
-
Fault in AL included to AL mask;
-
General FACP Fault;
-
A detector trigger in the AL included to AL mask;
-
Transition to FACP Alarm status.
Example
. You can program one of outputs, e.g. Out1, with the following activation condition:
Out1
=(Fire[AL1] AND Fire[AL2]) OR Fire[AL3]. At that the output shall go to active state if 2
loops AL1 and AL2 or one AL3 will go to Fire status.
5.2.6. K1..K4 low current programmable outputs
K1..K4 programmable outputs are designed to issue outcoming signals by complicated status
conditions of AL and FACP.
For each output AL mask can be set for those loops that will be involved in activation of output with
operation logics by AND/OR considering activation conditions.
To activate an output you should use from one to five conditions (event type):
- Fire in AL, included to AL mask;
-
Fault in AL included to AL mask;
-
General FACP Fault;
-
A detector trigger in the AL included to AL mask;
- Transition to FACP Alarm status.
Example.
You can program one of outputs, e.g. K11 with the following activation condition:
K1
=(Fire[AL1] AND Fire[AL2] OR Fire[AL3]. At that the output shall go to active state if 2 loops
AL1 and AL2 or one AL3 will go to Fire status.
Note
. By default activation conditions of outputs are set thus that:
AL1 and AL2 provoke activation of K1 output;
AL3 and AL4 – K2;
AL5 and AL6 – K3;
AL7 and AL8 – K4.
5.3 Main modes
5.3.1 General overview
The panel can operate simultaneously in Fire, Fault, Alarm, Disabled modes that are indicated by various
LED luminescence, different sound of internal sounder and by outputs statuses.
Luminescence of indicators differs with colour, repetition period (frequency of flashes) and porosity
(period/duration of flash impulses) depending on the mode.
The internal buzzer sounds differently in Fire, Alarm and Fault modes.
Switching on of the corresponding mode indicators and AL indicators in Fire, Fault, Disabled modes
coincides in frequency and phase.
The description of light and sound indication of all modes and statuses appears in Appendix 5.
5.3.2 Fire mode
The indicators of the corresponding zone and the Fire indicator synchronically flash with red colour, the
internal sounder issues the Fire signal, the Fire output («
Fire
») activates reporting the signal to CMS and
outputs to “
Light”
and
“Sound”
alarms activate in the Fire mode. In addition, “
Out1”, “Out2”,
1»..« 4»
outputs can be activated if appropriately set.