SPECIFICATIONS
Communication:
Hart version 6
Loop Power (excitation): 24 vdc
Output:
4-20mA dc, 2-wire
Loop Resistance:
500 ohms (max) at 24 vdc
Cable Recommended:
2 conductor; stranded, 18-24 AWG, shielded with ground
INSTALLATION
Hart board hardware for installation
to an IZMSG flowmeter
Qty: 4 – M3 x 10mm standoffs
(Included in kit)
1.) Remove the X9 terminal block from the Junction board indicated
to the right.
2.) Remove the 4 indicated screws holding the Junction board to the
Main circuit board (see manual AIC2040 page 1-5, Figure 1-5).
3.) Place the screws and washers to the side for reuse when
installing the Hart board.
4.) Install M3 x 10mm standoffs to the 4 Hart mount location
indicated on the Junction circuit board positions indicated
to the right.
5.) Fasten the Hart board to the Junction board using the screws
removed in step 2.
6.) Connect prewired CS3-BUS connector to corresponding X9
socket located on the Junction board.
Anderson Instrument Co., Inc.
156 Auriesville Rd.
Fultonville, NY 12072
Phone: 518-922-5315 or 800-833-0081
Fax:
518-922-8997 or 800-726-6733
Technical Bulletin
IZMSG HART Installation
Kit Part# 56705A0001
Rev. 1.0
Page 1 of 2
Doc 1178
+
-
24 VDC POWER
INPUT DEVICE
LOOP
+
LOOP
-
+
-
Hart
COMMUNICATION
DEVICE
NOTE: Loop must have 250 ohms
minimum resistance.
Prewired CS3-BUS connector.
IZMSG Hart
Transmitter Board
Secure ground
wire to 300-SMB1
upper left mount
with screw.
Zero Trim
1.) Apply loop power to the Hart transmitter board after
applying power to the IZMSG converter.
2.) Connect the Hart communication device across the
transmitter terminals. The signal loop must have at least
250 ohms resistance for Hart communication device function.
3.) Turn on the Hart communication device. Wait until
communications are established and the Home Menu is
displayed.
4.) If the Process Value is not within specification after
stabilization:
1. Select Calibration
2. Select D/A trim
3. Select “OK” to acknowledge WARN-LOOP remove from
auto control
4. Select “OK” to acknowledge connection of mA indicator
5. Select “OK” to acknowledge setting field deviation
output to 4mA.
6. Enter indicated mA value and acknowledge with
selecting “OK”
7. Acknowledge indicated mA adjustment with “YES/NO”
then select “OK”
8. Select “OK” to acknowledge setting field deviation
output to 20mA.
9. Enter indicated mA value and acknowledge with selecting “OK”
10. Acknowledge indicated mA adjustment with “YES/NO” then
select “OK
11. Select “OK” to acknowledge loop returning to original output
12. Select “OK” to acknowledge NOTE return to auto control
NOTE: Hart output will fault at 3.85mA with loss of IZMSG
signal.
NOTE: Disconnecting the CS-3 terminal while
operating the flowmeter will cause temporary
lose of measurement.
Содержание IZMSG
Страница 24: ...3 8 IZMSG Compact Electromagnetic Flowmeter AIC2071 Figure 3 8 Meter Body Converter Connections...
Страница 60: ...A 2 IZMSG Compact Electromagnetic Flowmeter AIC 2071 Converter...
Страница 61: ...Anderson Instrument Company A 3 AIC 2071...
Страница 62: ...A 4 IZMSG Compact Electromagnetic Flowmeter AIC 2071 Meter Body...
Страница 63: ...Anderson Instrument Company A 5 AIC 2071...
Страница 79: ......