3-6
IZMSG Compact Electromagnetic Flowmeter
AIC2071
Note:
The terminals in the meter body are spring compression terminals. To
make the connection, insert a 1/8" (3mm)
flat blade screwdriver into the opening on
the top of the terminal. Press down on the
screwdriver against the compression
spring to open the terminal while pushing
the ferrule on the end of each wire into
the terminal opening. It is necessary to
engage each wire of a multiwire cable
slightly before working the wires into full
engagement in the terminal.
2. Connect the conductor wires to the terminal locations inside the meter
body. See the following table.
Cable
Wire
Meter Body Terminal
Gray - Electrode Signal
Cable
red
14
white
16
black
18
shield
13
Black - Coil Drive Cable
white
11
black
12
To install the connection cables at the converter end:
1. Carefully measure the amount of cable needed to enter the correct converter
cable opening. Trim the excess length (see Cable Field Preparation in the
next subsection)
Note:
Make sure the cable is routed through the proper wire
opening. Use the correct wire entry hardware. See the
preceding subsection for additional information on correct
placement and use of wire entry hardware.
2. Connect the conductor wires to the correct terminal location inside the
converter. See the following table.
Содержание IZMSG
Страница 24: ...3 8 IZMSG Compact Electromagnetic Flowmeter AIC2071 Figure 3 8 Meter Body Converter Connections...
Страница 60: ...A 2 IZMSG Compact Electromagnetic Flowmeter AIC 2071 Converter...
Страница 61: ...Anderson Instrument Company A 3 AIC 2071...
Страница 62: ...A 4 IZMSG Compact Electromagnetic Flowmeter AIC 2071 Meter Body...
Страница 63: ...Anderson Instrument Company A 5 AIC 2071...
Страница 79: ......