Anderson Instrument Company
3-11
AIC2071
5. Route the AC power wires through the opening in the cover. Dress the AC
wires between the inside of the cover skirt and the power supply circuit
board.
6. Connect the AC power supply wires to the correct location on terminal
block XP: line to L and neutral to N.
7. Connect an earth ground to the terminal block XP at the location marked
PE. In most cases the green safety ground wire in 115 VAC, 3-wire service
will provide a path to earth ground.
Caution
Failure to connect an earth ground to the
terminal PE will cause the flow meter to
m alfunction.
8. Properly seal wire entry points in the converter enclosure and meter body
to prevent moisture intrusion.
WARNING!
Keep the fuse cover in place to prevent
exposure to electrical shock hazard.
Disconnect AC power to the converter
before making any wiring connections to
the converter or meter body.