3-10
IZMSG Compact Electromagnetic Flowmeter
AIC2071
Figure 3-8. Power Supply Jumper Configuration
AC Electrical Power Connections
To install the AC electrical power connections.
WARNING!
Do not apply electrical power to the
converter until all wiring connections are
completed and terminal locations verified.
1. Select a dedicated AC circuit for instrumentation. Do not select an AC
electrical supply circuit that is used for powering large machines or motors.
2. Route the AC power supply wire through conduit in accordance with local
regulations. Use a flexible whip of sufficient length to a fixed mounting
point to allow the cover of the converter to be opened for service or
inspection.
3. Open the cover of the converter to reveal the power supply on the inside
lower portion of the cover.
4. Make sure the jumper configuration matches the supply voltage. Change
the jumpers if required (see Figure 3-8).