Installation Procedures
The meter body installation procedures must be tailored to the specific site
and the size of the flowmeter. Select a location for the meter body using the
guidelines discussed in the previous subsection.
Install the meter body with a minimum of 5 pipe diameters of straight,
unobstructed pipe upstream from the meter body and
3
pipe diameters of
straight, unobstructed pipe downstream when measured from the inlet and
outlet of the meter body. No tees, elbows, valves, check valves, or other
devices that may cause turbulent flow can be within these lengths of straight
pipe.