Publication 1756-UM523F-EN-P - December 2006
Configure and Program the Controller
75
Actions
Action
Details
1. Get the size of your crossload data.
Use a Get System Value (GSV) instruction to read the REDUNDANCY object.
See Logix5000 Controllers General Instructions Reference Manual, publication
1756-RM003, for more information on the GSV and SSV instructions.
2. Estimate the crossload time.
Which controller do you have?
•
If ControlLogix5555, then crossload time = (0.0015 ms *
DINTs
) + 1 ms overhead
•
If ControlLogix5561, then crossload time = (0.0013 ms *
DINTs
) + 1 ms overhead
•
If ControlLogix5562, then crossload time = (0.0013 ms *
DINTs
) + 1 ms overhead
•
If ControlLogix5563, then crossload time = (0.0013 ms *
DINTs
) + 1 ms overhead
where
DINTs
is the size of tag data to be crossloaded, measured in 4-byte words.
For this information
Get this attribute
Data
Type
Description
•
Size of the last crossload
•
Size of the last crossload
if you had a secondary
chassis
LastDataTransfer
Size
DINT
This attribute gives the size of data that was or would have been
crossloaded in the last scan.
•
The size in DINTs (4-byte words).
•
You must configure the controller for redundancy.
•
You do not need a secondary chassis.
Is there a synchronized secondary chassis?
•
Yes — This gives number of DINTs that was crossloaded in the last
scan.
•
No — This gives number of DINTs that would have been crossloaded
in the last scan.
•
Size of the biggest
crossload
•
Size of the biggest
crossload if you had a
secondary chassis
MaxDataTransfer
Size
DINT
This attribute gives the biggest size of the LastDataTransfer Size
attribute.
•
The size in DINTs (4-byte words).
•
You must configure the controller for redundancy.
•
You do not need a secondary chassis.
•
To reset this value, use an SSV instruction with a Source value of 0.
Is there a synchronized secondary chassis?
•
Yes — This gives biggest number of DINTs that was crossloaded.
•
No — This gives biggest number of DINTs that would have been
crossloaded.
Содержание 1756-CNB/E
Страница 4: ...Publication 1756 UM523F EN P December 2006 Summary of Changes 4 Notes...
Страница 10: ...Publication 1756 UM523F EN P December 2006 10 Table of Contents...
Страница 26: ...Publication 1756 UM523F EN P December 2006 26 ControlLogix Redundancy System Overview Notes...
Страница 42: ...Publication 1756 UM523F EN P December 2006 42 Design the System Notes...
Страница 64: ...Publication 1756 UM523F EN P December 2006 64 Configure the System Redundancy Module Notes...
Страница 102: ...Publication 1756 UM523F EN P December 2006 102 Configure and Program the Controller Notes...
Страница 146: ...Publication 1756 UM523F EN P December 2006 146 Update Modules and Redundant Systems Notes...
Страница 162: ...Publication 1756 UM523F EN P December 2006 162 Set Up EtherNet IP Communication Across Subnets Notes...
Страница 168: ...Publication 1756 UM523F EN P December 2006 168 Convert an Existing System to Redundancy Notes...
Страница 178: ...Publication 1756 UM523F EN P December 2006 178 Redundant System Restrictions Notes...
Страница 185: ......