Publication 1756-UM523F-EN-P - December 2006
Update Modules and Redundant Systems
131
3. Open the SRM configuration tool for the
primary chassis.
A. Start RSLinx software.
B. From the Communications menu, choose RSWho.
C. Open the branches of your network until you find the 1757-SRM module in the primary
chassis.
D. Right-click the 1757-SRM module and choose Module Configuration.
4. Disqualify the secondary chassis,
A. Click Configuration.
B. Set Auto-Synchronization to Never.
C. Choose Apply and then Yes.
D. Click Synchronization.
F. Click OK.
Action
Details
E. Click Disqualify Secondary and then Yes.
The secondary chassis
is disqualified.
Содержание 1756-CNB/E
Страница 4: ...Publication 1756 UM523F EN P December 2006 Summary of Changes 4 Notes...
Страница 10: ...Publication 1756 UM523F EN P December 2006 10 Table of Contents...
Страница 26: ...Publication 1756 UM523F EN P December 2006 26 ControlLogix Redundancy System Overview Notes...
Страница 42: ...Publication 1756 UM523F EN P December 2006 42 Design the System Notes...
Страница 64: ...Publication 1756 UM523F EN P December 2006 64 Configure the System Redundancy Module Notes...
Страница 102: ...Publication 1756 UM523F EN P December 2006 102 Configure and Program the Controller Notes...
Страница 146: ...Publication 1756 UM523F EN P December 2006 146 Update Modules and Redundant Systems Notes...
Страница 162: ...Publication 1756 UM523F EN P December 2006 162 Set Up EtherNet IP Communication Across Subnets Notes...
Страница 168: ...Publication 1756 UM523F EN P December 2006 168 Convert an Existing System to Redundancy Notes...
Страница 178: ...Publication 1756 UM523F EN P December 2006 178 Redundant System Restrictions Notes...
Страница 185: ......