Publication 1756-UM523F-EN-P - December 2006
134
Update Modules and Redundant Systems
8. Reset the secondary CNB modules.
A. Cycle power to the secondary chassis.
B. On the Synchronization Status tab of the configuration tool, verify that the modules
show full compatibility.
9. Synchronize the secondary chassis.
A. Click Synchronization.
B. Click Synchronize Secondary and then Yes.
C. Wait for the chassis to synchronize.
10. Initiate a switchover.
Click Initiate Switchover and Yes.
11. Replace the CNB modules in the new
secondary chassis.
Repeat steps 6-8 for the CNB modules in the new secondary chassis.
Action
Details
The chassis are synchronized.
Содержание 1756-CNB/E
Страница 4: ...Publication 1756 UM523F EN P December 2006 Summary of Changes 4 Notes...
Страница 10: ...Publication 1756 UM523F EN P December 2006 10 Table of Contents...
Страница 26: ...Publication 1756 UM523F EN P December 2006 26 ControlLogix Redundancy System Overview Notes...
Страница 42: ...Publication 1756 UM523F EN P December 2006 42 Design the System Notes...
Страница 64: ...Publication 1756 UM523F EN P December 2006 64 Configure the System Redundancy Module Notes...
Страница 102: ...Publication 1756 UM523F EN P December 2006 102 Configure and Program the Controller Notes...
Страница 146: ...Publication 1756 UM523F EN P December 2006 146 Update Modules and Redundant Systems Notes...
Страница 162: ...Publication 1756 UM523F EN P December 2006 162 Set Up EtherNet IP Communication Across Subnets Notes...
Страница 168: ...Publication 1756 UM523F EN P December 2006 168 Convert an Existing System to Redundancy Notes...
Страница 178: ...Publication 1756 UM523F EN P December 2006 178 Redundant System Restrictions Notes...
Страница 185: ......