Configure and Program the Controller
Decide if You Want to Keep Test Edits after a Switchover
When you edit logic while online with the controller, the edits may
fault the controller and cause a switchover.
Test Edits
If test edits fault the primary controller, they will likely also fault the
secondary controller. To prevent faulting, any test edits are
deactivated (untested) during a switchover. As an option, you can
keep the edits active after a switchover.
Retention of Test Edits
Test Edit Options
Test Edits
If you want to
Then
Prevent an incorrect online edit from
faulting both the primary and secondary
controller
Do not retain test edits (default setting).
Keep test edits active during a switchover
(at the risk of faulting both controllers)
Retain test edits.
Содержание 1756-CNB/E
Страница 4: ...Publication 1756 UM523F EN P December 2006 Summary of Changes 4 Notes...
Страница 10: ...Publication 1756 UM523F EN P December 2006 10 Table of Contents...
Страница 26: ...Publication 1756 UM523F EN P December 2006 26 ControlLogix Redundancy System Overview Notes...
Страница 42: ...Publication 1756 UM523F EN P December 2006 42 Design the System Notes...
Страница 64: ...Publication 1756 UM523F EN P December 2006 64 Configure the System Redundancy Module Notes...
Страница 102: ...Publication 1756 UM523F EN P December 2006 102 Configure and Program the Controller Notes...
Страница 146: ...Publication 1756 UM523F EN P December 2006 146 Update Modules and Redundant Systems Notes...
Страница 162: ...Publication 1756 UM523F EN P December 2006 162 Set Up EtherNet IP Communication Across Subnets Notes...
Страница 168: ...Publication 1756 UM523F EN P December 2006 168 Convert an Existing System to Redundancy Notes...
Страница 178: ...Publication 1756 UM523F EN P December 2006 178 Redundant System Restrictions Notes...
Страница 185: ......