RK3000 High Frequency Power Supply
Operating Manual
Page 68 of 73
TABLE 1
PREPROGRAMMED LEVELS AND OPERATING RANGES
The Max Set Size and the LIMITS must be programmed for the control to energize. All
other parameters will operate on the preset values shown below. If the transformer-
rectifier control line voltage has been removed, the control will operate on the last set of
information entered when the line voltage has been restored.
Function
Preprogrammed
Value
Range
Keyboard Entry
Max Primary Current
001 A
1
– 500 A
1 amp increments
Max Secondary Current
0001 ma
1
– 3000 ma
1 milliamp increments
Max Secondary Voltage
01 kV
1
– 99 V
1 kilovolt increments
Primary Voltage Limit
400V
25-600 V
1 V increments
Primary Current Limit
000A *
1-500 A
1 A increments
Secondary Current Limit
0000MA *
1-3000 mA
1 mA increments
Secondary Voltage Limit
00KV *
1-99 kV
1 kV increments
Primary Under Voltage Trip
100V
20-300 V
1 V increments
Secondary Under Voltage Trip
20kV
05-99 kV
1 kV increments
Ramp
10
0.2-60 seconds
.1 second increments
Phase Back
20%
1-99%
1% increments
Pedestal
2
1-10 cycles
1 cycle increments
Quench Time
1
1-9 cycles
1 cycle increments
Quench Mode
0
0 or 1
0 = Arc, 1 = Arc & Spark
Process Sense
90
10-99seconds
1 second increments
Spark Rate Control
0
0 or 1
(0)Disable, (1) Enable
Spark Rate
24
2-200 SPM
1 SPM increments
Under Voltage Trip Delay Time
30
10-99
1 second increments
Under Voltage Trip Detection
0
0 or 1
(0) Primary, (1) Secondary
External Alarm Text
1,2,3,4
1 - 14
See Appendix III
External Alarm 1 - 4
1
0 or 1
(0) Nontrip, (1) Trip
ID Ranges
Keypad/Display Unit ID
001
001 - 250
1 unit increments
Interface Unit End ID Number
01
1
– 99
1 unit increments
Interface Unit Start ID Number
01
1 - ***
1 unit increments
Coordination System
0
0 or 1
(0) Disabled, (1) Enable
Coordination System End ID
Number
01
1 - 99
1 unit increments
Coordination System Start ID
Number
01
1 - ****
1 unit increments
Displays
Peak Reading (under construction)
-
-
-
Pre Spark Reading
0
0 or 1
(0) Disable, (1) Enable
Conduction Display
0
0 or 1
(0) Disable, (1) Enable
Averaged Readings
0
0 or 1
(0) Disable, (1) Enable
* These values will change to the values entered for the Max values.
** Three times the programmed Maximum Secondary Current.
*** Value entered for Interface Unit End ID Number
**** Valued entered for Coordination System End ID Number