RK3000 High Frequency Power Supply
Operating Manual
Page 45 of 73
Pressing “1” will bring up the MRC ID screen:
This screen is used to tell the TR control which of the microprocessor rapper controls
(MRC), if there are more than one, is to activate the TR control’s power down system.
The ID of the rapper control that is associated with each of the TR controls can be found
in the MRC Programming Data Sheets in the MRC manual.
Enter the numerical value corresponding to the desired ID number and press the ENTER
key. The screen will return to the Power Down Rapping Prompt screen.
Press the DOWN or UP keys to view more prompt screens or press ESC to return the
display to either the Electrical Reading Screen or the Device Status Screen depending on
the screen you were in prior to pressing the PROMPT key.
Rapping System Set-up for Motor Timers (Option)
Refer to Appendix II for programming instructions.
Spark Sensitivity
Press the PROMPT key and then the
key until the “Spark Sensitivity” Prompt Screen
appears.
Press ENTER and the ‘Spark Sensitivity” Parameter Screen will appear.
The normal operating level for the Spark Sensitivity parameter is 00. At that sensitivity,
sparks are only detected off the primary current signal. Any value entered from 1 to 20
will automatically cause the sparks to be detected off the secondary voltage signal. The
value entered (other than 0) is the amount of secondary voltage drop (in thousands of
volts) that will trigger spark detection within the control.
If the operating value is to be changed, simply press the numeric key(s) corresponding to
the new value desired (the old value will be overwritten), and press ENTER. If the
present operating value is acceptable, simply press ENTER without making any changes
Press the
or
keys to view more prompt screens or press ESC to return the display to
either the Electrical Reading Screen or the Device Status Screen depending on the
screen you were in prior to pressing the PROMPT key.
RED-01
MRC ID for Pwr Down
Range: 1-9
Enter: 1
RED-01
Spark Sensitivity
RED-01
Spark Sensitivity
Range: 0 - 20 KV
Enter: 00