RK3000 High Frequency Power Supply
Operating Manual
Page 42 of 73
Press the DOWN or UP keys to view more prompt screens or press ESC to return the
display to either the Electrical Reading Screen or the Device Status Screen depending on
the screen you were in prior to pressing the PROMPT key.
Under Voltage Setup
Press the PROMPT key and then the DOWN key unt
il the “Under Voltage Setup” Prompt
Screen appears.
RED-01
UV Setup
Press ENTER and the first “Under Voltage Setup” Parameter Screen will appear.
AVC-01
U V Trip Detection
0=Primary, 1=Secondary
Enter: 0
This screen allows the under voltage trip to be activated based on the primary voltage or
the secondary voltage.
If the present choice is to be changed, simply press the numeric key corresponding to the
new value (the old value will be overwritten) and press ENTER. If the present choice is
acceptable, simply press ENTER without making any changes. Whether a change is
made or not, after the ENTER key is pressed the “Primary Trip” Parameter Screen or the
“Secondary Trip” Parameter Screen will appear depending on the selection in the UV
Detection Screen.
RED-01
Primary UV Trip
Range: 25-600 volts
Enter:100
RED-01
Secondary UV Trip
Range: 10-99 kV
Enter: 20
These screens allow the voltage level, below which a control trip will occur, to be entered.
If the present choice is to be changed, simply press the numeric keys corresponding to
the new value (the old value will be overwritten) and press ENTER. If the present choice
is acceptable, simply press ENTER without making any changes. Whether a change is
made or not, after the ENTER key is pressed the
“UV Delay Time” Parameter Screen will
appear.
TR Name
UV Trip Delay Time
Range: 10-99 sec
Enter: 30