RK3000 High Frequency Power Supply
Operating Manual
Page 10 of 73
QUICK START CHART
For One-to One System Configuration
(See page 24)
A one-to-one system configuration is defined as a system where there is
one Keypad and Display Unit, and one Control Unit physically installed
on each control cabinet. If you have more than one Keypad and Display
Unit associated with more than one Control Unit see the Quick Start Chat
for a One-to Many Configuration (next page).
Not all parameters and operating modes need to be programmed in order
to get the control(s) up and running.
To get started quickly, for each
control cabinet, follow the instructions in the order that they appear
below.
1. Enter the Programming security code (page 24).
2. Program the Max Set Size (page 41).
3. Program the Limits (page 27).
The other parameters and operating modes have default values, based
on typical precipitator operation. They will allow the control and
precipitator to operate, but at less than optimum efficiency. All default
values should be reprogrammed, as needed, to optimize the precipitator
efficiency and minimize outlet emissions.
At this point all the control IDs and Names will be the same. Reprogram
the control ID set-up (page 25) to give each TR control a unique name, if
desired.