RK3000 High Frequency Power Supply
Operating Manual
Page 66 of 73
the relays assigned to Mode 2 can be On at the same time, however any
relay in Mode 1 can be On when any relay in Mode 2 is On. Mode 0 is
used to make the relay totally independent of any other relay so it will
operate based on its Interval and On Time without regard to other relay
times.
The Range of the Mode is 0 to 2. The present Mode is presented to the
right of the word “ENTER”. In this example the present Mode is 0.
If the Mode is to be changed, simply press the numeric keys
corresponding to the new value (the old value will be overwritten) and
press ENTER. If the present Mode is acceptable, simply press ENTER
without making any changes. Either way, the display will now change to
the Rapper 1 Power Down screen.
Power down refers to power down rapping. Power down rapping means
reducing the power to the TR control that energizes the area of the
precipitator the motor driven rappers are cleaning while the relay is
energized. The KV level the TR is reduced to is programmed under the
Power Down Rapping prompt.
If the power to the TR is to be reduced durin
g relay operation, press “1”
to enable Power Down. If it is not desirable to reduce the power during
relay operation, press “0” to disable Power Down. Your choice will
appear next to the word Enable.
After you have made your selection press the ENTER key and the
Rapper 1 Enable/Disable screen will appear.
This screen is used to choose whether or not this rapper relay will
operate or not. If it is Enabled, the relay will run through its Interval and
On Time as programmed. If it is Disabled, the relay will not operate
regardless of the Interval and On Time. Choose the desired operating
mode for this rapper relay by pressing a “0” or “1”. Your choice will
appear next to the word Enter.
After you have made your choice press the ENTER key and the Rapper 2
Interval Screen will appear. Program the operation of Rapper relay 2, 3,
and 4 in the same manner as above.
When the last screen for Rapper 4 (Rapper 4 Enable/Disable) has been
programmed and the ENTER key pressed the screen will return to the
Rapper System Setup prompt. Press the
↑ or ↓ keys to view more
prompt screens or press ESC to return the display to either the Electrical
Readings Screen or the Device Status Screen depending on the screen
you were in prior to pressing the PROMPT key.
RED-01
Rapper 1 Power Down
0=Disable, 1=Enable
Enter: 0
RED-01
Rapper 1
0=Disable, 1=Enable
Enter: 0