Section 3 – Quick Installation
3–3
Initial System Test
ACS access grants and egress grants are alarm type events in the alarm panel log. If you have
changed the default values for “Event Log Types” (alarm panel field 1*70) so that alarm type
events are not logged, the following procedure can not be used. To use this procedure, refer to
the
“Data Field Program Mode”
descriptions in your alarm panel installation and setup guide and
temporarily enable alarm type events in field 1*70 to perform this test.
Check the operation of the VistaKey to verify that the installed hardware is functional by
performing the following procedure.
1. Using any of the alarm control panel keypads, enter Installer
Code + # + 78. The keypad displays:
ACS TEST MODE
0 = quit
0
2. Press 2 on the keypad. The keypad displays:
ACS TEST MODE
GRANT ALL CARDS
2
3. Press [
✲
] on the keypad. The keypad starts beeping at a periodic
rated indicating the system is in the test mode and the keypad
displays:
GRANT ALL CARDS
ACS TEST MODE
4. Swipe any ADEMCO proximity card past the card reader. If the unit is properly installed,
the mag lock or door strike activates, and the green LED temporarily illuminates on the
card reader. If the test is successful, advance to step 5. If the mag lock or door strike does
not activate, and the green LED does not illuminate, do the following:
a. Exit the ACS TEST MODE by entering Installer Code + # +
78 + 0 + *. The keypad stops beeping and displays
:
****DISARMED****
READY TO ARM
b. Check all wiring to the units and that external power is applied.
c. Return to Step 1 and repeat the test.
5. If additional VistaKeys have been installed for additional access points, repeat step 4 at
the card reader for each of the additional access points.
6. Exit the ACS Test Mode by entering Installer Code + # + 78 +
0 + * at the keypad. The keypad stops beeping and displays:
****DISARMED****
READY TO ARM
7. Verify that all access points tested are logged in the alarm panel’s event log by using the
following procedure.
a. Using any of the alarm panel keypads, enter Installer Code
+ # + 60 to view the alarm panel control log. The keypad
displays:
ENTER 0= RECENT
1=COMPLETE DUMP
b. Press 1 on the keypad. The keypad displays:
SCAN LOG BY PART
0=NO 1-8=PART #
c. Press 0 on the keypad. The keypad displays:
ALARM EVENT LOG
TYPE CCC UUU
d. Press 3 on the keypad repeatedly until the keypad displays:
ALL EVENT LOG
TYPE CCC UUU
e. Press 8 on the keypad. The keypad display shows the most recent event in the log.
f. Press 1 on the keypad to step back through the event log to verify that all access points
tested are in the log. The first line of the log provides a partition number, date, and
time. The second line of the display for the access point test shows “ACS GRT” or “EGR
GRT” followed by a 3-digit zone number and user number of U999. Note that U999
Содержание VistaKey-SK
Страница 2: ......
Страница 6: ...vi...
Страница 8: ...viii...
Страница 40: ...VistaKey Installation Guide 4 10...
Страница 107: ......
Страница 108: ...165 Eileen Way Syosset New York 11791 Copyright 2000 PITTWAY CORPORATION l K4005 6 00...