Section 5 - Programming
5–31
025 REPORT CODE
1
st
01 2
nd
00
10
When you are programming for the #73 function, the response to
this entry does not affect operation.
Press [
✲
] repeatedly until the “INPUT TYPE” prompt appears.
025 INPUT TYPE
None
00
Enter the zone input type as 09 for Console.
Press [
✲
] to continue.
025 Cons ECP Addr
(00-30)
00
Enter the 2-digit ECP address of the keypad.
Press [
✲
] to continue.
025 ZT P RC
IN
L
27 1 10
C S 1
The summary screen for the zone appears.
Press
[
✲
]
to accept the zone information.
The alarm system control returns to the “ENTER ZONE NO.”
prompt. Enter “000” and then press [
✲
] to exit Zone Programming.
Exit #93 Menu Mode Programming.
The system has been set up for the #73 command to unlatch the access point programmed
when the command is issued by a valid user at the keypad.
Alarm System Levels of Authority
When you are installing a VistaKey in an alarm system, it is important to review the levels
of authority assigned to the users of the system. The Installer Level (Authority Level 0) and
the Master Level (Authority Level 1) can:
•
Enroll cards into the system
•
Issue all action commands listed in Table 5-1: Action Codes
For example, if the building contains four companies (see diagram below) and each company
has a Master Level user assigned, that user can assign cards for other companies and/or
control their access points by issuing action commands. Because of this, the highest level
assigned to any company should be Manager (Authority Level 2); the Master Level should
only be assigned to the user responsible for security in the whole building.
COMPANY B
(PARTITION 2)
COMPANY A
(PARTITION 1)
COMPANY C
(PARTITION 3)
COMPANY D
(PARTITION 4)
LOBBY
(COMMON LOBBY)
= READER