VistaKey Installation Guide
5–18
↓
Access Point Number
01 GP CONFIG
NORM OPEN
0
Enter 1 digit for the general purpose zone (VistaKey zone C)
configuration. This zone is normally used for a tamper when the
VistaKey cabinet requires supervision. Acceptable 1-digit entries
are as follows:
0 = normally open
1 = normally closed
2 = EOLR normally open
3 = EOLR normally closed
Press [
✲
] to accept the entry.
↓
Access Point Number
01 PREALARM TRIG
NOT ENABLED
0
The prealarm trigger prompt is used to define if the prealarm
trigger is to be enabled. If the prealarm trigger is enabled, the
trigger will be activated when the prealarm time begins (see
PREALARM TIME and ALARM TIMEOUT prompts above) and be
deactivated when the access point closes. This output can be used
for a door propped alarm.
Press 1 to enable the prealarm trigger output.
Press 0 to disable the prealarm trigger and make the trigger output
uncommitted.
↓
Access Point Number
01 TRIG MODE
NOT USED
0
The mode of operation of the trigger can be set to “discrete,” “one-
shot,” or “repeating.” A discrete trigger will become energized when
commanded on and will stay energized until commanded off. An
example of a discrete trigger is when a door is open and a timeout
occurs (door fault), the trigger turns on and it remains on until the
door is closed (fault removed). A one-shot trigger energizes once
when commanded on, stays on for the specified on time, then shuts
off. A repeating trigger output cycles on and off for the specified
amount of on time, off time, and for the specified number of repeat
counts. If the repeat count is set to zero, the cycling continues until
the trigger is commanded off.
Press 0 through 3 for the trigger action mode.
0 = not used (If you select 0, the system advances to the ACCESS
GROUP prompt below.)
1 = discrete (If you select 1, the system advances to the ACCESS
GROUP prompt below.)
2 = one-shot (If you select 2, the system advances to the “TRIG
ON TIME” prompt.)
3 = repeating (If you select 3, the system advances to the “TRIG
REPT CNT” prompt below.)
Press [
✲
] to accept the entry.
↓
Access Point Number
01 TRIG RPT CNT
Continuous
0
Enter 1 digit representing the number of repeated on/off cycles that
are output by the trigger function. If this number is set to 0, the
trigger repeats continuously until it is commanded off. Acceptable 1-
digit entries are as follows:
0 = continuous
4 = 4 cycles
1 = 1 cycle
5 = 5 cycles
2 = 2 cycles
6 = 10 cycles
3 = 3 cycles
7 = 25 cycles
Press [
✲
] to accept the entry.
Содержание VistaKey-SK
Страница 2: ......
Страница 6: ...vi...
Страница 8: ...viii...
Страница 40: ...VistaKey Installation Guide 4 10...
Страница 107: ......
Страница 108: ...165 Eileen Way Syosset New York 11791 Copyright 2000 PITTWAY CORPORATION l K4005 6 00...