Commissioning of the KNX Function via DCA (from ETS5)
Product manual 2CKA00xx73xxxxx
│
65
■
Send indoor sensor temperature
Options:
Do not send
On change
Cyclically
On change and cyclically
The parameter is used to specify whether or when the temperature values of the indoor sensor
are passed on to other devices.
■
Cycle time for automatic transmission of the internal sensor temperature [sec.]
Options:
Setting option from 5 - 3600 seconds
The parameter is used to specify the intervals at which the temperature values of the indoor
sensor are passed on to other devices.
Notice
This parameter is only available if parameter "Send indoor sensor temperature"
has been parameterized to "cyclic".
Haptic and acoustic feedback
■
Acoustic signal at press of button
Options:
Activated
Deactivated
When the checkbox is activated an acoustic signal sounds during the press of a button.
■
Default setting of volume of acoustic signal [%]
Options:
Setting option from -128 - +127 K
The parameter us used to specify the volume of the acoustic signal at the press of a button.
Notice
This parameter is only available if parameter "Send indoor sensor temperature"
has been parameterized to "cyclic".
■
Sensitivity of the haptic feedback
Options:
Inactive
Soft
Middle
Hard
The parameter us used to specify the sensitivity of the haptic feedback.