KNX control elements and application parameters
Application "Fault and alarm messages" - Global settings
Product manual 2CKA00xx73xxxxx
│
188
10.18.3 Enable export
Options:
Deactivated
Activated
The parameter is used to specify whether the messages can be exported under the fixed file
name in CSV format. The messages can then be exported via the application page.
–
Deactivated
: No export. No additional parameters available.
–
Activated
: The following parameter appears:
File name [.CSV]
:
Options: <Text>
The parameter is used to change the file name of the export file.
The length of the name is limited to 60 characters.
10.18.4 Automatic archiving at an acknowledgement
Options:
Deactivated
Activated
The parameter is used to specify that after acknowledgement in the application page the
message is archived immediately and is no longer displayed in the alarm list.
–
Deactivated
: No automatic archiving after acknowledgement. The following supplementary
parameter is available:
Automatic archiving as soon as the alarm is no longer active
.
Options:
Deactivated
Activated
–
Deactivated
: No automatic archiving when the alarm is no longer active.
–
Activated
: The message is archived and displayed as soon as the alarm is no longer
active.
–
Activated
: The message is archived in the application page automatically after the
acknowledgement.
10.18.5 Sound for alarm
Options:
Setting option from 1 - 5
The parameter is used to specify which signal tone is to be played during the display of the
message. Five different signal tones are available for selection.
10.18.6 Sound for Notice
Options:
Setting option from 1 - 5
The parameter is used to specify which signal tone is to be played during the display of the
message. Five different signal tones are available for selection.