KNX control elements and application parameters
Operation of "RGBW" control element“
Product manual 2CKA00xx73xxxxx
│
129
White activation via:
Options:
Warm/cold objects
Temperature/brightness (Hue) objects
The parameter is used to specify how the white lamps are controlled.
–
Warm/cold objects
: The activation takes place via separate channels, i.e. via a "Warm
White" (WW) and a "Cold White" (CW) channel. Prerequisite: The lamp to be controlled
has different channels (e.g. 2 stripes).
–
Temperature/brightness objects (Hue)
: If no separate channels are available (e.g.
Philips Hue), activation takes place via the colour temperature and brightness. The
communication objects are named the same for both types of activation; however,
different values are sent (either brightness and colour temperature or Cold White and
Warm White).
Switching On/Off via:
Options:
1 object
2 objects
The parameter is used to specify the On/Off control.
–
1 Object
: Setting when the lamp has only one channel (e.g. Philips Hue).
–
2 Objects
: Setting when the lamp has several channels (RGB and White separated, e.g.
two stripes), separate ON/OFF switching via data points.
Switched On -> preset value:
Options:
Deactivated
Activated
–
Deactivated
: No presets are sent when the lamp is switched on.
–
Activated
: The stored presets are sent when the lamp is switched on.
Switched Off -> RGB value 0,0,0:
Options:
Deactivated
Activated
–
Deactivated
: No RGB values are sent when the lamp is switched off.
–
Activated
: The RGB values (0,0,0) are sent when the lamp is switched off. This
parameter is important for lamps that do not contain a "Switch" object.
–
WW/CW
: Used for lamps with Warm White and Cold White component. The following
supplementary parameters are available:
White activation via:
Options:
Warm/cold objects
Temperature/brightness (Hue) objects
The parameter is used to specify how the white lamps are controlled.
–
Warm/cold objects
: The activation takes place via separate channels, i.e. via a "Warm
White" (WW) and a "Cold White" (CW) channel. Prerequisite: The lamp to be controlled
has different channels (e.g. 2 stripes).