KNX control elements and application parameters
Application "Logical functions"
Product manual 2CKA00xx73xxxxx
│
206
–
2-byte value [0 - 65535]
: A value is sent as 2-byte value without a sign, e.g. actuating
value or time interval. No additional parameters available.
–
2-byte floating point
: A value is sent as 2-byte floating point value, e.g. a temperature
value, a time duration, a performance or a consumption value. No additional parameters
available.
–
4-byte value [-2147483648 - 2147483647]
: A value is sent as 4-byte value with a sign,
e.g. actuating value or time difference. No additional parameters available.
–
4-byte value [0 - 4294967295]
: A value is sent as 4-byte value without a sign, e.g.
actuating value. No additional parameters available.
–
14-byte text
: Makes it possible to send a text. No additional parameters available.
Saving input signal during blocking
:
Options:
Deactivated
Activated
See the explanation above.
–
Temperature comparator
: This function can be used to compare temperature values. The
following parameters are displayed:
Name of channel
:
Options: <Name>
Naming of the channel. The length of the name is limited to 60 characters.
Type of comparator
:
Options:
Temperature with a constant
2 temperatures
This function can be used to compare two temperatures. Or a temperature can be
compared with an internal specified temperature value (constant).
–
Temperature with a constant
: This function makes an input available with a 2-byte
communication object. On this object temperature telegrams are received and
compared, which are sent from a KNX temperature sensor for example.
The following parameters are displayed:
Input 2 [°C]
:
Options:
Setting options from -30 - +70
This parameter is used to specify the value with which the temperature at input 1 is to
be compared.
Hysteresis
:
Options:
Setting options from 0.5 - 10
–
2 temperatures
: This function makes two separate inputs with 2-byte communication
objects available. On these objects temperature telegrams are received and compared
with each other, which are sent from KNX temperature sensors. No additional
parameters available.