KNX control elements and application parameters
Application "Internal RTC"
Product manual 2CKA00xx73xxxxx
│
228
10.24.48 Control of additional heating stage — Additional heating type
Options:
PI continuous, 0 – 100% and PI PWM, On/Off:
■
Area (e.g. floor heating) 4°C 200 min
■
Convector (e.g. heater) 1.5°C 100 min
■
Free
configuration
Fan coil:
■
Fan coil 4°C 90 min
■
Free
configuration
Multiple heating types (panel heating, convector heating or fan coil) with preset parameters are
available to the user.
– If the required heating type is not available, individual parameters can be specified in the
free configuration.
Note
This parameter is only available when "Control value type" parameter for the
additional stage is set either on "PI continuous, 0 – 100%", "PI PWM, On/Off“
or "Fan coil".
10.24.49 Control of additional heating stage — P-component (x 0.1°C)
Options:
Setting option between 10 - 100
The P-component refers to the proportional range of a control. It fluctuates around the setpoint
value and can be used to influence control speed of a controller. The smaller the setpoint, the
faster the controller responds. However, to avoid the risk of an overshoot, this value should not
be set too low. A P-component from 0.1 to 25.5 K can be set.
Note
This parameter is only available when "Control value type" parameter for the
additional stage is set either on "PI continuous, 0 – 100%", "PI PWM, On/Off“ or
"Fan coil". The "Additional heating type" parameter must be set on "Free
configuration".