KNX control elements and application parameters
"Display" control element
Product manual 2CKA00xx73xxxxx
│
164
Text x for value [0 - 255]
:
Options:
Setting option from 0 - 255
The parameter is used to set the status value at which text x is displayed.
Notice
8 parameters "Text x at value [0 - 255]" are available which can be set as
required.
Text x
:
Options: <Text>
The parameter is used to specify the text that is displayed.
The length of the text is limited to 60 characters.
Notice
8 parameters "Text x" are available which can be set as required.
10.13.6 Type of display element — Value display — Size of the button
Options:
1 column
2 columns
The parameter is used to specify whether the display element occupies one column (one button
or control frame) or two columns (two buttons or control frames).
10.13.7 Type of display element — Value display — Object type
Options:
1-byte value [0% - 100%]
1-byte value [0 - 255]
1-byte value [-128 - 127]
2-byte value [0 - 65535]
2-byte value [-32768 - +32767]
2-byte floating point
4-byte value [0 - 4294967295]
4-byte value [-2147483648 - 2147483647]
4-byte floating point
14-byte text
Parameter "Object type" is used to specify the size of the communication object.
–
1-byte value [0% - 100%]
: A value is sent as 1-byte value without a sign (percentage value).
–
1-byte value [0 - 255]
: A value is sent as 1-byte value without a sign, e.g. actuating value,
angle or brightness value.
–
1-byte value [-128 - 127]
: A value is sent as 1-byte value with a sign, e.g. actuating value.
–
2-byte value [0 - 65535]
: A value is sent as 2-byte value without a sign, e.g. actuating value
or time interval.