10.24.10 Heating control — I-component (min.)
Options:
Setting option between 0 - 255
The I-component refers to the reset time of a control. The integral component has the effect of
moving the room temperature slowly toward, and ultimately reaching, the setpoint value.
Depending on the type of system used, the reset time has to have different values. In general,
the more inactive the overall system, the greater the reset time.
Note
This parameter is only available when "Control value type" parameter is set
either on "PI continuous, 0 – 100%", "PI PWM, On/Off“ or "Fan coil". In addition,
the "Heating type" parameter must be set on "Free configuration".
10.24.11 Heating control — Extended settings
Options:
Deactivated
Activated
– This parameter enables additional functions, e.g. "Status object heating".
10.24.12 Basic stage heating
Note
Only available when the "Extended settings" parameter under "Heating control"
is set on "Yes".
10.24.13 Basic stage heating — Status object heating
Options:
Deactivated
Activated
– The parameter enables the "Status heating" communication object.
10.24.14 Basic stage heating — Mode of the control value
Options:
Normal
Inverse
The mode of the control value can be used to adapt the control value to de-energised opened
(normal) or de-energised closed (inverse) valves.
–
Normal
: Value 0 means "Valve closed".
–
Inverse
: Value 0 means "Valve open".