KNX control elements and application parameters
Application "Internal RTC"
Product manual 2CKA00xx73xxxxx
│
233
10.24.60 Basic stage cooling - PWM cycle cooling (min)
Options:
Setting option between 1 - 60 minutes
In PI PWM, On/off the control value percentage values are converted into a pulse-interval
signal. This means that a selected PWM cycle will be divided into an on-phase and an off-phase
based on the control value. Accordingly, a control value output of 33% in a PWM cycle of 15
min. results in an On-phase of five minutes and an Off-phase of 10 min. The time for a PWM
cycle can be specified here.
NOTE
This parameter is only available when the "Control value type" parameter is set
on "PI PWM, On/Off“.
10.24.61 Basic stage cooling — Maximum control value (0 - 255)
Options:
Setting option between 0 - 255
The maximum control value of the PI controller defines the maximum value outputted by the
controller. If a maximum value under 255 is chosen, the value will not be exceeded, even if the
controller calculates a higher control value.
Note
This parameter is only available when "Control value type" parameter is set
either on "PI continuous, 0 – 100%", "PI PWM, On/Off“ or "Fan coil".
10.24.62 Basic stage cooling — Minimum control value for basic load (0 to 255)
Options:
Setting option between 0 - 255
The minimum control value of the PI controller defines the minimum value output by the
controller. If a minimum value greater than zero is chosen, the controller will not output a lower
value, even if it calculates a value that is lower. This parameter can be used to set a basic load,
e.g. for operating surface cooling. Even if the controller calculates the control value zero, a
cooling medium will flow through the cooling area to prevent the floor from heating up. Under
"Settings of basic load", it is also possible to define whether this basic load will be permanently
active or whether it will be switched by the "Basic load" object.
Note
This parameter is only available when "Control value type" parameter is set
either on "PI continuous, 0 – 100%", "PI PWM, On/Off“ or "Fan coil".