KNX control elements and application parameters
Application "Internal RTC"
Product manual 2CKA00xx73xxxxx
│
250
10.24.106
Setpoint settings — Hysteresis for switchover heating/cooling (x 0.1°C)
Options:
Setting option between 5 - 100
This parameter specifies the one-sided hysteresis for switching between heating and cooling
when "Setpoint heating comfort = Setpoint cooling comfort" is active. If the room temperature
exceeds the setpoint temperature value plus hysteresis, the system switches to cooling. If the
room temperature falls below the setpoint temperature value minus hysteresis, the system
switches to heating.
Note
This parameter is only available when the "Setpoint heating comfort = Setpoint
cooling comfort" parameter is set on "Yes".
10.24.107
Setpoint settings — Setpoint temperature for heating and cooling comfort (°C)
Options:
Setting option between 10 - 40
Specifies the comfort temperature for heating and cooling when people are present.
Note
This parameter is only available when the "Control function" parameter is set on
"Heating and cooling" or "heating and cooling with additional stages".
10.24.108
Temperature reading — Operating mode for fault
Options:
Cooling
Heating
In the event of a failure of the actual temperature measurement, the device will no longer be
able to independently specify the heating/cooling operating type. As a result, the operating type
best suited to protecting the building will be selected.
Note
This parameter is only available when the "Control function" parameter is set on
"Heating and cooling" or "heating and cooling with additional stages".