background image

Installation instructions

for contractors

VIESMANN

Vitosol F
Type SV and SH

Flat-plate collector for elevated installation

VITOSOL F

5727 904 GB

10/2015

Dispose after installation.

Содержание SH

Страница 1: ...Installation instructions for contractors VIESMANN Vitosol F Type SV and SH Flat plate collector for elevated installation VITOSOL F 5727 904 GB 10 2015 Dispose after installation ...

Страница 2: ...qualified electrician Regulations to be observed National installation regulations Statutory regulations for the prevention of accidents Statutory regulations for the protection of the envi ronment Codes of practice of the relevant trade associations All relevant safety regulations as defined by DIN EN DVGW VDE and locally applicable standards a ÖNORM EN and ÖVE c SEV SUVA SVTI SWKI and SVGW Worki...

Страница 3: ...culating collector row clearance z 7 Installation information 8 3 Installation sequence Installing the collector supports 9 Installing the collector 9 Fitting the connection set and collector temperature sensor 10 Installation 11 Commissioning 13 Index 5727 904 GB ...

Страница 4: ...w component or In conjunction with a tool Clean the sur face Dispose of component correctly Dispose of component at a suitable collec tion point Do not dispose of component in domestic waste Intended use The collectors provide central heating backup and solar backup for DHW heating They are only intended to be installed and operated in sealed systems that comply with EN 12976 and EN 12977 with due...

Страница 5: ... observe the installation instructions Failure to observe these instructions can change functions endanger life and limb of the user or third parties and will result in an exclusion of liability Incorrect usage also applies if components in the sys tem are modified from their intended use e g through direct DHW heating in the collector Adhere to statutory regulations especially concerning the hygi...

Страница 6: ...or Vitosol F types SV and SH 6 4 2 3 5 8 7 1 9 1 5 7 5 1 5 7 5 1 SV 60 Fig 1 1 Collector support with footplates 2 Washer 7 8 4 mm 3 Hexagon nut M 8 4 Hexagon bolt M 8 x 20 5 Retaining bracket 6 Clamping bracket 7 Joining plate 8 Cross brace 9 Hexagon bolt M 8 x 25 Components 5727 904 GB ...

Страница 7: ... angled 7 22 mm 90 qZ Support sleeve Sensor well set comprising qZ Support sleeve qU Locking ring fitting tee 7 22 mm qI Sensor well qO Strain relief fitting wP Thermal insulation Calculating collector row clearance z When installing several collectors in series maintain clearance z to prevent undesirable shading z β α α Fig 3 z Collector row clearance α Collector angle of inclination β Angle of t...

Страница 8: ...the maximum load and distance from the edge of the roof for the on site substructure to DIN 1055 Installation on concrete slabs A see fig 4 Remove any gravel or similar from the installation area cover the surface with protective building mats and position support slabs on top of these mats Installation on steel beams B see fig 4 Install the on site substructure at right angles to and horizontally...

Страница 9: ... 2200 1838 998 910 760 x mm 597 597 597 1921 1921 1921 y mm 480 480 480 480 480 480 Installing the collector Note on collector position The side with the type plate must be on the outside of the first and last collector If just 1 collector is used fit the pipework at the side opposite the type plate side Please note The connection pipes must be free of any signs of damage Lubricate O rings only wi...

Страница 10: ...king ring fitting All pipes must be cut at right angles and deburred Push the union nut and the locking ring onto the pipe and lightly lubricate the threads with oil Push the pipe into the locking ring fitting as far as it will go Initially tighten union nut by hand then tighten with an open ended spanner by a further revolution Please note Connection pipes and plugs must not display any damage Lu...

Страница 11: ...ed with heat transfer medium immediately after installation Protect collectors from insolation by covering them up Installation Please note Incorrect installation can lead to collector dam age Use only gunmetal or brass fittings and copper pipes for the installation Never step on collectors Never solder on or near the collectors Fitting the connection set and collector cont 5727 904 GB ...

Страница 12: ...e glycol resistance Hemp connections insufficiently gas tight Equip the system to EN 12975 with an expansion vessel safety valve and circulation pump The expansion vessel must be approved to DIN 4807 The diaphragms and seals of the expansion vessel and safety valve must be suitable for the heat trans fer medium To calculate the pre charge pressure see the Vitosol service instructions For operation...

Страница 13: ...13 For commissioning the solar thermal system see the Vitosol service instructions Commissioning 5727 904 GB ...

Страница 14: ...14 5727 904 GB ...

Страница 15: ...15 5727 904 GB ...

Страница 16: ...hropshire TF1 7YP GB Telephone 44 1952 675000 Fax 44 1952 675040 E mail info uk viessmann com Viessmann Werke GmbH Co KG D 35107 Allendorf Telephone 49 6452 70 0 Fax 49 6452 70 2780 www viessmann com 5727 904 GB Subject to technical modifications ...

Отзывы: