Chapter 5 – Programming
Installation and Start-up Guide for NPBA-01
5-2
Table 5-1 The ACS 600 parameters to be set on NPBA-01 installation.
Parameter
Alternative Settings
Default
Setting
Recommended
Setting
98.2 COMM.MODULE
YES; NO
NO
YES
51.1 MODULE TYPE
NPBA SW1.0
51.2 PROFIBUS MODE
FMS; DP-PPO1; DP-PPO2;
DP-PPO3; DP-PPO4; DP-PPO5
DP-PPO1
51.3 STATION NUMBER
2 to 126
2
51.4 BIT RATE SELECT
9.6KBIT; 19.2KBIT; 93.75KBIT; 187.5KBIT;
500KBIT; 1.5MBIT; AUTO
AUTO
51.5 WRITE PPO
DATA SET SEL
0 to 255
0
51.6 READ PPO
DATA SET SEL
0 to 255
0
10.1 EXT1 STRT/STP/DIR
NOT SEL; DI1; ...; DI6,5; KEYPAD;
COMM.MODULE
DI1,2
COMM.MODULE
10.2 EXT2 STRT/STP/DIR
NOT SEL; D1; ...; DI6,5; KEYPAD;
COMM.MODULE
NOT SEL
COMM.MODULE
10.3 DIRECTION
FORWARD; REVERSE; REQUEST
FORWARD
REQUEST
11.2 EXT1/EXT2 SELECT
DI1; ...; DI6; EXT1; EXT2; COMM.MODULE
EXT1
COMM.MODULE
11.3 EXT REF1 SELECT
KEYPAD; AI1; ...; MAX(AI2,AI3);
DI3U,4D(R); ...; DI5U,6D; COMM.MODULE
AI1
COMM.MODULE
11.6 EXT REF2 SELECT
KEYPAD; AI1; ...; MAX(AI2,AI3);
DI3U,4D(R); ...; DI5U,6D; COMM.MODULE
KEYPAD
COMM.MODULE
12.1 CONST SPEED SEL
NOT SEL; D1 (SPEED1); DI2 (SPEED2);
DI3 (SPEED3); DI4 (SPEED4);
DI5 (SPEED5); DI6 (SPEED6); DI1,2;
DI3,4; DI5,6; DI1,2,3; DI3,4,5; DI4,5,6;
DI3,4,5,6
DI5,6
NOT SEL
15.1 ANALOGUE OUTPUT1
NOT USED; P SPEED; ...; CONTROL DEV
SPEED
15.6 ANALOGUE OUTPUT2
NOT USED; P SPEED; ...; CONTROL DEV
CURRENT
16.1 RUN ENABLE
YES; DI1; ...; DI6; COMM.MODULE
YES
COMM.MODULE
16.4 FAULT RESET SEL
NOT SEL; DI1; ...; DI6; COMM.MODULE
NOT SEL
COMM.MODULE
21.3 STOP FUNCTION
COAST; RAMP
COAST
RAMP
30.18 COMM FAULT FUNC
NO; FAULT; CONST SP 15;
LAST SPEED
FAULT
30.19 COMM FLT TIME-OUT
0.1 to 60 s
1.00