Chapter 5 – Programming
Installation and Start-up Guide for NPBA-01
5-6
D1, ... D6
The External control location to be used is determined by the state of
the specified digital input. 0V DC on the selected digital input = EXT1;
24V DC on the selected digital input = EXT2.
COMM.MODULE
(Recommended Setting)
The selection between EXT 1 and EXT 2 is done through the
communication module (Control Word bit 11).
11.3 EXT REF1 SELECT
This parameter defines the source of the reference for External control
location 1 (see Parameter 11.2).
KEYPAD
The control panel is the source of the reference.
AI1, ... , MAX (AI2, AI3)
The analogue inputs (one or more) specified by the parameter value
are the source of the reference. For details on the use of the analogue
inputs, see the
ACS 600 Programming Manual.
DI3U,4D(R), ... ,DI5U,6D
The digital inputs (one or more) specified by the parameter value are
source of the reference. For details on the digital inputs, see the
ACS
600 Programming Manual.
COMM.MODULE
(Recommended Setting)
The communication module is the source of the reference.
11.6 EXT REF2 SELECT
This parameter defines the source of the reference for External control
location 2 (see Parameter 11.2).
KEYPAD
The control panel is the source of the reference.
AI1, ... , MAX (AI2, AI3)
The analogue inputs (one or more) specified by the parameter value
are source of the reference. For details on the use of the analogue
inputs, see the
ACS 600 Programming Manual.
DI3U,4D(R), ... ,DI5U,6D
The digital inputs (one or more) specified by the parameter value are
the source of the reference. For details on the use of the digital inputs,
see the
ACS 600 Programming Manual.
COMM.MODULE
(Recommended Setting)
The communication module is the source of the reference.
12.1 CONST SPEED SEL
This parameter defines which digital inputs are used to select Constant
Speeds.
NOT SEL
(Recommended Setting)
Constant speed function disabled. This setting is recommended as this
parameter overrides external reference selections.
D1 (SPEED1), ..., DI3,4,5,6
Constant speeds selected with digital inputs. For details, see the
ACS 600 Programming Manual.