![ABB NPBA-01 Скачать руководство пользователя страница 22](http://html.mh-extra.com/html/abb/npba-01/npba-01_installation-and-startup-manual_2755022.webp)
Chapter 5 – Programming
5-3
Installation and Start-up Guide for NPBA-01
NPBA-01 Module
Activation
The NPBA-01 Adapter Module must be activated to establish the
communication between the ACS 600 and the module.
98.2 COMM.MODULE
The connection with the NPBA-01 PROFIBUS Adapter Module and the
ACS 600 is activated with this parameter.
YES
The connection between the NPBA-01 and the ACS 600 is active.
NO
The connection between the NPBA-01 and the ACS 600 is inactive.
After the module is activated, the configuration parameters of the
NPBA-01 are automatically copied from the adapter module to the
configuration table of the ACS 600.
PROFIBUS
Connection
Configuration
Parameter Group 51 includes the parameters for module address and
mode. The user needs to adjust the parameters only if the default
values have to be changed.
Note: The new parameter settings take effect only after the module
power supply is switched off and then on again.
Table 5-2 Parameter Group 51 COMMUNICATION MODULE.
Parameter
Alternative Settings
Default Setting
51.1 MODULE TYPE
NPBA SW1.0
51.2 PROFIBUS MODE
FMS; DP-PPO1;
DP-PPO2; DP-PPO3;
DP-PPO4; DP-PPO5
DP-PPO1
51.3 STATION NUMBER
2 to 126
2
51.4 BIT RATE SELECT
9.6KBIT; 19.2KBIT;
93.75KBIT; 187.5KBIT;
500KBIT; 1.5MBIT; AUTO
AUTO
51.5 WRITE PPO
DATA SET SEL
0 to 255
0
51.6 READ PPO
DATA SET SEL
0 to 255
0