Chapter 5 – Programming
5-5
Installation and Start-up Guide for NPBA-01
D1, ..., D6,5
The drive receives the Start, Stop and Direction commands through the
digital inputs. For details on the use of the digital inputs, see the
ACS
600 Programming Manual.
COMM.MODULE
(Recommended Setting)
The drive receives the Start, Stop and Direction commands through the
communication (fieldbus adapter) module. The rotation direction of the
motor is determined by the selected reference.
10.2 EXT2
STRT/STP/DIR
This parameter defines the source of the for the Start, Stop and
Direction commands for External control location 2 (see Parameter
11.2).
NOT SEL
No source is selected for the Start, Stop and Direction commands.
D1, ..., D6,5
The drive receives the Start, Stop and Direction commands through the
digital inputs. For details on the use of the digital inputs, see the
ACS
600 Programming Manual.
COMM.MODULE
(Recommended Setting)
The drive receives the Start, Stop and Direction commands through the
communication (fieldbus adapter) module. The rotation direction of the
motor is determined by the selected reference.
10.3 DIRECTION
FORWARD, REVERSE
The rotation direction of the motor is fixed to FORWARD or REVERSE.
REQUEST
(Recommended Setting)
The rotation direction is defined with Parameter 10.1 EXT1 STR/STP/
DIR and Parameter 10.2 EXT2 STR/STP/DIR, or by keypad push-
buttons. The selection is overridden if Parameter 11.3 EXT REF1
SELECT or Parameter 11.6 EXT REF2 SELECT is set to AI1/JOYST
or AI2/JOYST or to COMM.MODULE.
11.2 EXT1/EXT2
SELECT
This parameter defines the active External control location for the Start,
Stop and Direction commands and for the reference. The parameter
sets one of the digital inputs or the communication module to select
between EXT1 and EXT2. Alternatively, the parameter fixes either
EXT1 or EXT2 as the active External control location.
EXT1
External control location 1 is selected as the active External control
location. Parameter 10.1 defines the source of the Start, Stop and
Direction Commands. Parameter 11.3 defines the source of the
reference.
EXT2
External control location 2 is selected as the active External control
location. Parameter 10.2 defines the source of the Start, Stop and
Direction Commands. Parameter 11.6 defines the source of the
reference.